Maintenance Of F*-Jb - Pepperl+Fuchs F-JB Series Manual

Fieldbus junction boxes/segment protectors
Table of Contents

Advertisement

F2-JB-#.I, F*-JB-#.*
Maintenance of Cable Glands
10.2
Maintenance of F*-JB***-...CGB and CGS Cable Glands
Connectorizing Cables Using F*...CGB and CGS Cable Glands
1. Strip the insulation of the cable up to about 160 mm.
2. Loosen the cap nut from the device and push it onto the cable.
3. Remove the inner plastic piece and slip it onto the cable: move it far enough over the cable,
so it completely surrounds the cable sheath. 
Ensure that no cable sheath protrudes behind the inner plastic piece.
29