Pepperl+Fuchs F-JB Series Manual page 25

Fieldbus junction boxes/segment protectors
Table of Contents

Advertisement

F2-JB-#.I, F*-JB-#.*
Connection Layout
1
2
Figure 9.5
1
Trunk In
2
Spur
3
Trunk Out
4
Shield
Terminal
1+
2-
3s
4+
5-
6s
7+
8-
9s
T
S
Earth
The "3s" and "9s" terminals are internally connected to terminal "T". Terminal "6s" is connected
internally with terminal "S". The terminals "Earth" are connected to the external grounding
clamp.
3
4
Layout of the connections of the internal terminal strip in the F4 housing (1 output)
Function
Trunk, input (Trunk In) +
Trunk, input (Trunk In) -
Trunk, input (Trunk In), shield
Spur (Spur) +
Spur (Spur) -
Spur (Spur), shield
Trunk, output (Trunk Out) +
Trunk, output (Trunk Out) -
Trunk, output (Trunk Out), shield
Trunks, shield
Spurs, shield
Equipotential bonding