Wiring
Reliable acquisition by the fail-safe I/O module
The following table lists the minimum duration of the sensor signals for the fail-safe
I/O module. This depends on the parameter settings for the short-circuit test and
the input delay in STEP 7 (see Section 8.2).
Table 5-1
Short-Circuit Test
Parameter
Deactivated
Activated
Reliable acquisition by the safety program on the F-CPU
You will find information on the times necessary for correct acquisition of the
sensor signals in the safety program in Chapter 9 of the system description
Safety Engineering in SIMATIC S7.
Technical Specifications of the Sensors
Please refer to Chapter 8 for the technical specifications relating to the choice of
sensors.
5-6
Minimum Duration of the Sensor Signals to Allow Correct Acquisition by the
Fail-Safe I/O Module
Assigned Input Delay
3 ms
9 ms
12 ms
ET 200eco Distributed I/O Station Fail-Safe I/O Module
15 ms
23 ms
37 ms