Technical specifications
8.8 Specifications
Supply voltage
Rated voltage
Range, permissible
Transients, maximum permissible
Time between two transients,
minimum
Current consumption
Typical
Constant current, maximum
Power on current surge I
Fuse, internal
Miscellaneous
Realtime clock
96
KTP1000 Basic Color DP
t
2
KTP1000 Basic Color DP
KTP1000 Basic Color PN
+24 VDC
19.2 to 28.8 V (–20%, +20%)
35 V (500 ms)
50 s
Approx. 600 mA
Approx. 1000 mA
Approx. 0.2 A
s
2
Electronic
KTP1000 Basic Color PN
Yes, unbuffered
KTP400 Basic, KTP600 Basic, KTP1000 Basic, TP1500 Basic
Operating Instructions, 08/2008, A5E01075587-01
TP1500 Basic Color PN
Approx. 800 mA
Approx. 1000 mA
Approx. 0.2 A
s
2
TP1500 Basic Color PN