Set Up Communications - Daikin BACnet Series Installation Manual

Table of Contents

Advertisement

Set Up Communications

Setting BACnet™ communications properties is required only if the
BACnet Thermostat is integrated into a network with other BACnet
controllers. Entering the communications properties requires
entering Password 2.
Table 8: Set Up Communications
Procedure
Starting display
Change the network communication properties
IO-DAPPS
Steps
1. Start at the temperature display.
2. Enter Password 2. The display changes to the MAIN menu display.
1. From the MAIN menu, press either the ▲ or ▼ button to
select COMM.
2. Press Enter. The COMM menu opens up.
3. Choose and set the following properties.
• DEVICE ID – This is the BACnet device instance. The device
instance must be within the range of 1 to 4,194,302.
• MAC – The MAC address must be in the range of 1 – 127.
• BAUD – Set to match other devices on the BACnet MS/TP
network. The choices are Auto, 9600, 19200, 38400, or 76800.
NOTE: After changing a communication property the BACnet
Thermostat will reset.
NOTE: If setting up with the MicroTech Integrated System contact a
Daikin representative for the appropriate values.