Commissioning
3.1 Connecting Power
5. Wire input power connector P8 for AC or DC power depending on power supply provided
Note
Power Supply connector wires should be stripped AWG 12-18 stranded wire or solid
conductors.
Terminal Number
1
2
3
6. Plug input power connector P8 into connector J8 and secure using two captive connector
7. Secure power input cable with cable clamp to prevent wire breakage.
8. Replace Rear Housing Cover and tighten setscrew.
9. Connect the power cables to the appropriate power source previously selected from the
Note
Loosen Wire Clamp Screw, insert stripped end of wire and then retighten.
Table 3- 1
USA
EU
18
as shown below. Insert wires into wire entry holes and secure by tightening wire clamp
screws (see figure below).
1010X-6SS2
Hot
Neutral
Ground
mounting screws as indicated below.
tables above and power up unit (100-250 VAC @ 50/60 Hz or 9-36 VDC).
Wire Clamp Screws
Connector Mounting Screws
Stripped Wire
Figure 3-1
Input Power Connector (P8) Wiring
Color Codes
HOT
BK
BR
1010X-6ZNS2
Positive
Negative (Gnd)
Ground
NEU
GND
WH
GRN
BL
Y/GRN
Operating Instructions (Compact), 12/2008, CQO:QSG010 Revision A
1010X-6ZPS2
Positive
Negative (Gnd)
Ground
SITRANS FUH1010 Quick Start