WI850D GEM-P800 Installation Instructions
System Troubles
Keypad Beeps or
Zone LED
SYSTEM
j
ON
Flashes
1 Beep
2 Beeps
3 Beeps
1-6
4 Beeps
1-6
5 Beeps
1-4
6 Beeps
1-4
7 Beeps
1-6
24
System Trouble
Condition
1
AC Power Failure
2
Low Battery
Communication
3
Failure/PCPreset Fail
4
Telephone Line Cut
1
Bell/Siren line Cut
2
2-wire Fire Trouble
Rcvr Fail-to-Respond/Rcvr
3
Tamper
4
Receiver Jam
Wireless
Transmitter Low Battery
Wireless
Transmitter
Supervisory Failure
Wireless Smoke Detector
Low Battery
Wireless Smoke Detector
Supervisory
Zone Trouble
This trouble will occur if AC power is not present. Ensure that the transformer is connected to an unswitched power source.
If there has been a recent power failure, the battery may be partially depleted and must be recharged by the control panel. If the
trouble does not go away in 24 hours, replace the battery.
The system was not able to report to central station. Check panel programming and telephone line wiring. The trouble will clear after
it has been acknowledged by viewing the system trouble as long as the telephone line has passed a line cut test (tested automatically
by the panel).
The Panel did not sucsessfully connect and download/upload with the commputer running PCPreset - check Auto
Download ID number, Callback Number or PCPreset Setup.
The telephone line has failed. If telephone service has been temporarily interrupted, the trouble will clear when restored and
acknowledged by viewing the system trouble.
There is a problem with the Bell or Siren wiring. EOL2.2K resistor must be installed.
There is a problem with the wiring of the Fire Zone.
The receiver is not responding to the panel. The red LED on the receiver should be flashing, refer to WI850. The cover is off the
receiver causing a tamper signal to be transmitted.
A signal is blocking the normal reception of transmissions from the wireless devices. Ensure that the green LED on the receiver is not
on continuously, refer to receiver manual WI850.
The battery in the wireless transmitter is low and should be replaced. This transmitter is on the zone corresponding to the number of
the zone light flashing. The replacement battery for the GEM Trans2 door/window transmitter and the GEM PIR wireless motion
detector is the Duracell DL123A. (2 required for the GEM-PIR) WARNING: Replace batteries only with the same type as specified
above. Use of another battery may present a risk of fire or explosion. Do not recharge or disassemble battery or dispose of in fire.
The panel has not received a supervisory signal from the transmitter within the time programmed. Check Wireless Supervisory Timer
[16] Programming. Check the placement of the transmitter and receiver, refer to WI850.
The battery in the wireless smoke detector is low and should be replaced. This wireless smoke detector should be marked with a
number corresponding to the number of the zone light flashing. The replacement batteries required are *Duracell 9 Volt Alkaline (2).
The panel has not received a supervisory signal from the wireless smoke detector within the programmed time. Check Wireless
Smoke Supervisory Timer [17] Programming. Check the placement of the wireless smoke detector and receiver, refer to WI850.
The panel has one or more of the following 3 possible troubles: Zone Short, Transmitter Tamper or Dual Tech Self Test Fail.
Cause/Action