Installation Procedure
1.
Access the optional module slots on the drive. Whenever
necessary, refer to the Hardware Manual of the drive for
instructions on removing any covers.
2.
Insert the module carefully into the slot marked "DDCS"
on the RMIO board until the retaining clips lock the
module into position.
3.
Fasten the screws included in the package. Note that
correct installation of the screws is essential for fulfilling
the EMC requirements and for proper operation of the
module.
4.
Lead the fibre optic cables from the external device to the
appropriate channel(s) of the RDCO. Inside the drive,
route the cables as shown in its Hardware Manual. Make
sure the cables are not kinked or laid against sharp
edges. Observe colour coding so that transmitters are
connected to receivers and vice versa. In case multiple
devices are to be connected to one channel, they must
be connected in a ring.
Technical data
Module types: RDCO-01(C), RDCO-02(C), RDCO-03(C)
Degree of protection: IP 20
Ambient conditions: The applicable ambient conditions
specified for the drive in its Hardware Manual are in effect.
ABB Oy
AC Drives
P.O. Box 184
FIN-00381 Helsinki
FINLAND
Telephone:
+358 10 22 11
Fax:
+358 10 222 2681
Internet:
www.abb.com
Connectors:
20-pin pinheader
4 transmitter/receiver connector pairs for fibre optic cable.
Type: Agilent Technologies Versatile Link. Communication
speed: 1, 2 or 4 Mbit/s
Operating voltage: +5 V DC ±10%, supplied by the RMIO
board of the drive
Current consumption: 200 mA max.
Electromagnetic immunity: IEC 1000-4-2 (limits: industrial,
second environment); IEC 1000-4-3; IEC 1000-4-4;
IEC 1000-4-6
Electromagnetic emissions: EN 50081-2; CISPR 11
Dimensions (mm):
ABB Inc.
Drives & Power Products
16250 West Glendale Drive
New Berlin, WI 53151
USA
Telephone:
262 785-8378
800 243-4384
Fax:
262 780-5135