Siemens SINUMERIK 840D sl Ctrl-Energy System Manual page 24

Hide thumbs Also See for SINUMERIK 840D sl Ctrl-Energy:
Table of Contents

Advertisement

Ctrl-E Analysis
3.3 Commissioning the PLC for Ctrl-E Analysis
DB1001
Name: SentronPac
DB1001.DBX0.2
DB1001.DBX0.3
DB1001.DBX1.0
DB1001.DBX2.0
DB1001.DBX3.0
DB1001.DBD4
DB1001.DBD8
DB1001.DBD12
DB1001.DBD16
DB1001.DBD20
DB1001.DBD24
DB1001.DBD28
DB1001.DBD32
DB1001.DBD36
DB1001.DBD40
DB1001.DBD44
24
Signal
Meaning
direction
PLC -> HMI
Imported active ener‐
gy is read from SEN‐
TRON PAC
PLC -> HMI
Exported active ener‐
gy is read from SEN‐
TRON PAC
PLC -> GP
Measuring request to
PLC basic program
HMI -> GP
Measurement is run‐
ning
PLC -> HMI Power display shown
in status display
PLC -> HMI
Manual value
GP -> HMI
Total active power
MeasAuto
Measured imported
== 0:
active energy in kWh
PLC -> HMI
to HMI
MeasAuto
== 1:
GP -> HMI
MeasAuto
Measured exported
== 0:
active energy in kWh
PLC -> HMI
to HMI
MeasAuto
== 1:
GP -> HMI
PLC -> GP
Total active power
in watts from SEN‐
TRON
PLC -> GP
Imported active ener‐
gy at tariff 1 (F) in Wh
from SENTRON
PLC -> GP
Exported active ener‐
gy at tariff 1 (F) in Wh
from SENTRON
GP -> HMI
Imported active ener‐
gy in kWh current day
to HMI
GP -> HMI
Exported active ener‐
gy in kWh current day
to HMI
GP -> HMI
Imported active ener‐
gy in kWh previous
day to HMI
GP -> HMI
Exported active ener‐
gy in kWh previous
day to HMI
Identifier
FeedInEnergyReadSP
FeedBackEnergyReadSP
MeasAuto
MeasAct
EStateOn
ManualValue
ActivePowerItem
ActiveEnergyItem
ReactiveEnergyItem
ActivePowerSentron
ActiveEnergySentron
ReactiveEnergySentron
ActiveEnergyDay
ReactiveEnergyDay
ActiveEnergyPrevDay
ReactiveEnergyPrevDay
System Manual, 01/2015, 6FC5397-0EP40-5BA2
Format
BOOL
BOOL
BOOL
BOOL
BOOL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
Ctrl-Energy