INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS
Installation: Mounting of the unit
3
4
5
Material damage (e .g . water damage)
Warning
Heat recovery of air with a high moisture content leads to condensation in the heat ex-
WARNING
changer. Condensate must be led into a drain, as it otherwise can damage the floor under
the unit.
Caution
Connect the drain hose to the
used drain outlet and secure the
connection with a hose clamp.
The drain hose must be supplied
with a min. 100 mm siphon (op-
tion A or B).
Guide the hose to a drain and
make sure it does not get
exposed to frost.
Fill the siphon with min. 0.5
L water.
HCV 400 only
Mount the cable clamp into
the whole at the bottom of
the unit
Guide the drain hose through
the cable clamp, in order to
create the siphon.
Make sure that the drain hose is installed according to the current operating mode.
Check the siphon periodically especially during summer period and make sure that it is
filled with water as recommended.
A
B
33