Fieldbus Modules For Abb Drives; Common Recommendations - ABB ACS310 Quick Start Manual

Plc and drives integration using modbus rtu
Hide thumbs Also See for ACS310:
Table of Contents

Advertisement

 
Quickstart Guide
 
ABB PLC and drives integration using Modbus RTU
 
Fieldbus modules for ABB drives 
The  following  ABB  drives  Modbus  RTU  modules  have  an  option  to  activate  built‐in  end  termination  and  pull‐
up/pull‐down resistors. 
RMBA‐01 (used with for instance ACS550 and ACS800) 
FSCA‐01 (used with for instance ACS880 and ACSM1) 
The following ABB drives Modbus RTU module does not have an option to activate built‐in end resistors including 
pull‐up/pull‐down resistors. 
FMBA‐01 (used with for instance ACS355) 
Since  the  built‐in  end  termination  of  the  modules  (RMBA‐01  and  FSCA‐01)  automatically  also  activates  pull‐
up/pull‐down resistors, it is recommended to skip the built‐in option. 
It is recommended to connect a separate end termination resistor to the first node (i.e. the PLC COM interface) 
and the last node (i.e. the last drive on the bus). 
For connection examples, see chapter "Installation examples". 
 
Common recommendations 
Note! The following bullets are only recommendations and no general rules. 
Installation where total cable length is more than 50 m 
o Use CPU AC500 rather than AC500‐eCo or AC500‐eCo with TK506 RS 485 isolator for COM1. 
Installation where there is a risk that ground connections in different nodes could vary in voltage potential 
(typically in ship installations or with cable lengths more than 50 m). 
o Use CPU AC500 and do not connect ground cable, only shield → 2‐wire solution, or use AC500‐eCo 
with TK506 RS 485 isolator for COM1. 
When AC500‐eCo is used 
o Use  of  3‐wire  connection  is  recommended  because  the  COM  interface  is  not  opto‐isolated,  
or use AC500‐eCo with TK506 RS 485 isolator for COM1. 
o Use 
of 
or use AC500‐eCo with TK506 RS 485 isolator for COM1. 
Cable type 
o Use  only  cables  with  twisted  pair  wires  and  braided  shields.  Foil  shields  are  not  robust  enough, 
cannot be contacted well and have poor HF (High Frequency) properties. 
o Ground the cable shield directly with a clip when entering the switch‐gear cabinet. Do not cut the 
shield until the cable reaches the connected module. 
o The connection between the PE bar and the shield bar must have low impedance. 
o Use ABB cable TK505 when suitable for easy installation. 
Modbus RTU 
cable 
length 
more 
‐ 8 ‐ 
than 
50m 
should 
 
 
be 
realized 
with 
PLC and drives integration  