Quickstart Guide
 
ABB PLC and drives integration using Modbus RTU
 
 
Starting up ACSM1 drives with FSCA­01 Modbus RTU adapter 
 
Minimum required parameter settings (based on factory default settings) 
Parameter  Description 
50.01 
FBA ENABLE 
51.02 
PROTOCOL/PROFILE 
51.03 
STATION ID 
51.04 
BAUD RATE 
51.05 
EFB PARITY 
52.01 
FBA DATA IN1 
52.02 
FBA DATA IN2 
53.01 
FBA DATA OUT1 
53.02 
FBA DATA OUT2 
51.27 
FBA PAR REFRESH 
10.01 
EXT1 START FUNC 
12.01 
EXT1/EXT2 SEL 
24.01 
SPEED REF1 SEL 
10.08 
FAULT RESET SEL 
 
Optional parameter settings 
51.06 
MODBUS TIMEOUT 
51.07 
TIMEOUT MODE 
50.02 
COMM LOSS FUNC 
51.27 
FBA PAR REFRESH 
(25.02) 
SPEED SCALING 
 
Modbus RTU 
Setting 
Comment 
Enable 
Activates fieldbus module 
ABB Drives 
Communication profile "ABB Drives" 
Classic 
[Address] 
Modbus RTU node address of the drive 
19.2 kbit/s 
Transfer rate of the link. Same baud rate must be 
(example) 
defined in the Modbus RTU master. 
8 NONE 1 
Parity and stop bits. Same parity and stop bits 
(example) 
must be defined in the Modbus RTU master. 
Status word as Data Word 1 from the drive 
Actual speed as Data Word 2 from the drive 
Control word as Data Word 1 to the drive 
Speed reference as Data Word 2 to the drive 
REFRESH 
Updates fieldbus settings (groups 50 to 53) 
FBA 
Fieldbus interface as source for start and stop 
P.02.12 bit15  Fieldbus interface as source to switch to EXT2 
control location 
FBA REF1 
Fieldbus interface as source for speed reference 
P.02.12 bit 8 
Fieldbus interface as source for fault reset 
[optional] 
Time between communication break detection 
and the selected action. 1 = 100 ms. 
CONTROL 
How the drive reacts to a fieldbus communication 
WRITE 
break. 
[optional] 
Defines the drive operation after the 
communication loss monitoring awakes. 
REFRESH 
Updates fieldbus settings (groups 50 to 53) 
[Scale max] 
Max speed/frequency scaling value (used in 
function block/visualization input 
"SPEED_REF_MAX"). Must be less or equal to drive 
parameter max speed/frequency. 
‐ 20 ‐ 
 
 
PLC and drives integration  