User Manual
Alarm
Low online rack
num
BMS
Comm
Fault Alarm
BMS
Fault
Alarm
BMS Alarm
10.2.3 Alarm Information on BCP
Alarm
BCP Alarm(including
BCP
fault,
alarm,
emergency stop)
Possible
causes
For the standard
battery, the alarm
occurs when the
online
Rack
number is lower
than
the
set
"Rack Num".
Communication
between
the
BMS
and
the
local
controller
failed.
The
battery
system or Rack
is faulty.
The
battery
system or Rack
gives an alarm.
Possible causes
A fault or an alarm
occurs in the external
devices connected to the
BCP,
such
conditioner and smoke
sensor.
Measures
1. Check whether
the batteries are
faulty.
2. Check whether
the
related
parameter of the
local controller is
appropriately set.
1. Check whether
the communication
cable
connecting
the BMS and the
local controller is
firmly in place.
2. Check whether
the IP address and
Modbus address of
the
BMS
are
correctly set.
3. Check whether
the serial port via
which the BMS is
connected to the
local controller is
correctly
configured.
Refer
to
the
measures
for
battery fault.
Refer
to
the
measures
for
battery alarm.
Measures
Check whether the devices
connected to the BCP,
such as the air conditioner
and smoke sensor run in
as
air
the normal state.
If a fault such as smoke
sensor
occurs or fire fighting is
10 Troubleshooting
Note
-
-
-
-
overtemperature
39