10 Troubleshooting
Alarm
One or More
High
Battery
Level2
Battery Group
DC V-Diff too
Large
38
Possible
causes
Battery
voltage/SOC
is
higher than the
"Vbat Uplimit2".
For multiple of
BCPs,
or
the
system in which
battery DC sides
are
directly
connected
in
parallel, "Battery
Direct
Connect
Voltage Value" is
greater than the
set value.
Measures
2. Check whether
the
protection
parameter is set to
an
appropriate
value.
1. Stop charging
2. Check whether
the
protection
parameter is set to
an
appropriate
value.
1. Check whether
the parameter is
set
to
an
appropriate value.
2. Check whether
the system voltage
difference between
battery
racks
whose DC sides
are connected in
parallel is relatively
large.
User Manual
Note
zero-power
operation if there is
no standby state),
but the charging
power
is
not
affected.
In
the
off-grid
mode,
the
local
controller
will
control the system
to shut down.
In
the
on-grid
mode,
the
local
controller
will
control the PCS to
enter the standby
state (or control the
PCS
to
perform
zero-power
operation if there is
no standby state),
but the charging
power
is
not
affected.
In
the
off-grid
mode,
the
user-side
EMS
needs to stop the
external
power
being fed into the
system.
When the alarm
occurs, the local
controller does not
respond
to
the
instruction sent by
the customer EMS
to close the BMS
contactor.