Setting
Configure
Available
Default
item
Submenu
Settings
Setting
[0%]
(Disable)
ECO
003
0%
[10%]
Mode*
[15%]
(Enable)
[DIS]
(Disable)
Bypass
004
Enable
Mode**
[ENA]
(Enable)
[DIS]
(Disable)
Converter
005
Disable
Mode
[ENA]
(Enable)
*)
When operating in ECO Mode, the efficiency of UPS is higher than that in online mode,
but transfer time should not be 0ms
**)
When operating in Converter Mode, the frequency of output should be always 50Hz
or 60Hz, but load capacity will be derated by 40%.
*)
This function would be set as 0% when Converter Mode is enabled.
**)
UPS has no bypass when Converter Mode is enabled.
18
LCD Display
5.5 Event ID descriptions
Event ID
Description of Cause
Bus Start Fail: DC-DC converter or bus sensing circuit
E01
failed.
E02
Bus Volt High: DC-DC converter failed.
E03
Bus Volt Low: DC-DC converter failed.
E04
Bus Unbalanced: DC-DC converter failed.
E06
INV Start Fail: Inverter circuit failed.
INV Volt High: Inverter circuit or output voltage sensing
E07
circuit failed.
INV Volt Low: The load may be too heavy or inverter
E08
circuit failed.
E09
INV Short: The inverter circuit failed.
Bat Volt High: The external battery module connection is
E11
wrong, or the charger failed.
E12
Bat bad: Batteries failed.
E14
Over Load: UPS is overloaded.
Fan Fail: The ventilation hole has been covered, or the
E18
fans can't work.
Over Temperature: High ambient temperature, or the
E19
ventilation hole has been covered.
A62
Bat low: Battery voltage low.
A66
EPO Off: Missing the EPO connection
High Temperature: High ambient temperature, or the
ventilation hole has been covered. This is shown only
A68
when start up UPS.
19