Summary Table - Samsung SINGLE AC MNMSEH/EU Series Technical Data Book

Msp duct for europe (r410a, hp)
Table of Contents

Advertisement

4. Summary Table

Indoor Units
Performance Characteristics
Net
Model Code
Weight
(kg)
AC052MNMSEH
30.0
AC071MNMSEH
30.0
AC100MNMSEH
33.0
AC120MNMSEH
47.8
NOTE
• Sound data is based on cooling operation.
Electric Characteristics
Model
Indoor Unit
Outdoor Unit
AC052MNMSEH
AC052MXASEH
AC071MNMSEH
AC071MXASEH
AC100MNMSEH
AC100MXASEH
AC120MNMSEH
AC120MXASEH
NOTE
• MCA : Minimum circuit amperes
• MFA : Maximum fuse amperes
• Select wire size based on the value of MCA
Capacity
Cooling
Heating
(kW)
(kW)
Max.
6.0
6.6
Std.
5.0
5.5
Min.
0.95
0.66
Max.
8.0
9.0
Std.
6.8
7.5
Min.
1.75
1.2
Max.
12.0
12.0
Std.
9.5
10.8
Min.
2.0
2.0
Max.
14.0
17.0
Std.
12.0
13.0
Min.
2.9
2.75
Outdoor Unit
Rated
Voltage range
Hz
Volts
Min. Max.
50
220 to 240
198
264
50
220 to 240
198
264
50
220 to 240
198
264
50
220 to 240
198
264
Airflow
Fan Speed
(CMM)
High
15.0
Mid.
14.2
Low
13.5
High
18.0
Mid.
15.8
Low
13.5
High
29.0
Mid.
24.5
Low
20.0
High
34.0
Mid.
29.0
Low
24.5
Input Current (Amperes)
Outdoor Unit
Indoor Unit
Cooling
Heating
13
13
3.5
20
20
3.5
22
22
3.5
24
24
3.5
Sound Pressure Level
Sound Power Level
(dBA)
(dBA)
31
55
28
25
33
57
30
27
35
62
32
29
37
64
34
31
Power Supply
Total
MCA(A)
16.5
16.5
23.5
23.5
25.5
25.5
27.5
27.5
-
-
-
-
-
-
-
-
MFA(A)
18.2
25
28
30
9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents