14. Installation
Indoor Unit
5 Select the insulation of the refrigerant pipe.
• Insulate the gas side and liquid side pipe, noting the
insulation thickness that must differ according to the
pipe size.
• Standard: Less than an indoor temperature of 30°C,
with humidity at 85%. If installing in a high humidity
environment, use one grade thicker insulator by
referring to the table below. If installing in an
unfavourable environment, use thicker one.
• The heat-resistance temperature of the insulator must
be more than 120°C.
Standard
Pipe
Pipe size
(Less than
30°C, 85%)
Ø6.35 to
Ø9.52
Liquid
pipe
Ø12.7 to
Ø19.05
Ø6.35
Ø9.52
Gas pipe
Ø12.70
Ø15.88
Ø19.05
• When installing insulation in the places and conditions
below, use the same insulation that is used for high
humidity conditions.
<Geological condition>
High humidity locations such as shorelines, hot springs,
lake or riversides, and ridges (when part of the building is
covered by earth and sand)
<Operation purpose condition>
Restaurant ceiling, sauna, swimming pool etc.
<Building construction condition>
Ceilings frequently exposed to moisture and cooling are
not covered. For example, pipes installed at a corridor of a
dormitory and studio or near an exit that opens and closes
frequently.
Places (where the pipes are installed) that are highly humid
due to a lack of ventilation.
Insulation type
(heating/cooling)
High humidity
Remarks
(Over 30°C,
85%)
EPDM, NBR
9t
9t
13t
13t
The internal
13t
19t
temperature
is higher
than 120°C.
19t
25t
Step 10 Installing the drain hose and drain pipe
1 Push the supplied drain hose as far as possible over the
drain socket.
2 Tighten the metal clamp as shown in the picture.
3 Wrap the supplied large sealing pad over the metal clamp
and drain hose to insulate and fix it with clamps.
4 Insulate the complete drain piping inside the building
(field supply).
If the drain hose cannot be sufficiently set on a slope, fit
the hose with drain raising piping (field supply).
5 Push the drain hose up to insulation when connecting the
drain hose to drain socket.
Metal clamp
Large seailng pad
Drain hose
Drain socket
Drain hose
Drain pipe
Be sure to bond the drain
hose and the main pipe.
PVC Tube Joint
+ VP25 (OD: 32 mm, ID: 25 mm)
Drain pipe
47