Indoor Unit
• You must have 20 mm or more space between the ceiling
and the bottom of indoor unit. Otherwise, the noise from
the vibration of indoor unit may bother the user. When the
ceiling is under construction, the hole for check-up must
be made to take service, clean and repair the unit.
• It is possible to install the unit at an height of between
2.2~2.5 m from the ground, if the unit has a duct with a
well defined lenght (300 mm or more), to avoid fan motor
blower contact.
• If you install the cassette or duct type indoor unit on the
ceiling with humidity over 80%, you must apply extra 10
mm of polyethylene foam or other insulation with similar
material on the body of the indoor unit.
Step 3 Optional: Insulating the body of the
indoor unit
D
A
Thickness: more than 10mm
AC052MNMSEH
Indoor
AC071MNMSEH
Unit
1150 X 480 X 260
A
1150 X 260
B
1150 X 260
C
480 X 260
D
480 X 260
Insulate the front and back side in proper size at the
Front/
same time when insulating the suction duct and
Back
discharge duct.
NOTE
• Insulate the end of the pipe and some curved area by
using separate insulator.
• Insulate the discharge and suction part at the same time
when you insulate connection duct.
42
AC100MNMSEH
AC120MNMSEH
1150 X 480 X 320
1200 X 650 X 360
1150 X 320
1200 X 360
1150 X 320
1200 X 360
480 X 320
650 X 360
480 X 320
650 X 360
(Unit: mm)
Step 4 Installing the indoor unit
When deciding on the location of the air conditioner with the
owner, the following restrictions must be taken into account
1 Place the pattern sheet on the ceiling at the spot where
you want to install the indoor unit.
NOTE
• Since the diagram is made of paper, it may shrink or
stretch slightly due to temperature or humidity. For this
reason, before drilling the holes maintain the correct
dimensions between the markings.
2 Insert bolt anchors. Use existing ceiling supports or
construct a suitable support as shown in figure.
B
C
Hole in anchor
Hole in plug
3 Install the suspension bolts depending on the ceiling type.
Concrete
Suspension bolt (M8) - field supply
Insert
Ceiling support