Coaxial PPs Vent System (continued)
1
Vent System
Vent System
Vertically Vented
Room Air
Independent Operation
1
PPs coaxial vent material must be ULC S-636 certified for Category IV boilers. Do not mix non-ULC S-636 with ULC S-636 venting.
2
Order 1 Mounting Clip for each straight length of vent pipe installed.
"
Do not include first 90° elbow in equivalent vent length calculations (this applies to all vent materials).
"
A maximum of 5 elbows may be installed in the vent system; do not exceed maximum equivalent vent length.
"
Always follow Viessmann venting installation instructions 5368 815.
B
B
A
A
A
Combustion Air Intake
B
Flue Gas Outlet
Vent System Diameter
Maximum Equivalent
Length (EqL)
1 Boiler Vent Pipe Adaptor
60/100
Adaptor, coaxial
60/100 to 80/125
(not shown)
Adaptor, coaxial
60/100 to 100/150
(not shown)
2 90° Elbow
EqL=1.6ft. / 0.5m
6 Mounting Clip
2
(each)
8 Sliding Coupling
1.25ft. / 0.4m
9 Straight Pipe
2
1.6ft. / 0.5m
2
Straight Pipe
3.3ft. / 1m
45° Elbow (Set of 2)
EqL=1ft. / 0.3m
Vent Termination
3.9ft. / 1.2m
Roof Flashing
and Storm Collar
(B-Vent material or better)
60/100
80/125
100/150
82 / 25
98 / 30
118 / 36
included with boiler
7424 112
7424 113
7424 094
7424 095
7424 096
7424 109
7424 110
7424 111
7424 106
7424 107
7424 108
7424 088
7424 089
7424 090
or
or
7424 091
7424 092
7424 093
7424 097
7424 098
7424 099
7424 103
7424 104
7424 105
field
supplied
Appendix
Diameter
ft. / m
Order No.
Order No.
Order No.
Order No.
Order No.
Order No.
or
Order No.
Order No.
Order No.
21