System Layout 3
Vitodens 100-W, WB1B 10-26, 10-35 with DHW storage tank and one heating circuit
AV
PRV
Y
4xpipe Ø
or 12" / 305mm
Fig. 15
IMPORTANT
Primary pump
must pump into
the boiler (as illustrated).
Please note!
The use of a low-loss header is
recommended if the water flow rate is
less than 1.7 GPM / 400 ltr/h or more
than 6.2 GPM / 1400 ltr/h.
The low-loss header is available as an
accessory part.
IMPORTANT
D
HW supply and return piping between boiler DHW connections and the Viessmann DHW tank connections, shall be a minimum of
1" nominal pipe diameter (irrespective of the ¾" DHW connection outlet sizes provided on the boiler and the DHW tank). This
ensures that the head of the pump is fully utilized to overcome the resistance of the DHW heat exchanger coil and to provide
sufficient water flow to the boiler heat exchanger. In non-Viessmann DHW tank applications, perform, in addition to the above,
accurate calculations for DHW tank coil pressure drop versus boiler pump head to ensure sufficient water flow to the boiler heat
exchanger. Failure to heed the above instructions may cause boiler short-cycling and inadequate DHW supply.
TPV
Y
Maximum Flow Rates
Model
WB1B
10-26
∆ ∆ ∆ ∆
t
83,000 108,000
Output
Btu/h
30 ºF rise (GPM)
5.5
35 ºF rise (GPM)
4.7
40 ºF rise (GPM)
4.2
Installation Examples
AV Air vent
PRV Pressure relief valve
TPV Temperature and pressure relief
valve
Vitodens 100-W gas-fired
condensing boiler
External boiler/DHW controller (field
supplied)
Heating circuit
Heating circuit pump (field supplied)
DHW storage tank
DHW tank temperature aquastat or
sensor
DHW circulating pump (field
supplied)
Closely spaced tees, 4xpipe Ø
or 12" / 305mm
Expansion tank
Primary pump (boiler circuit, field
supplied) with low-loss header only
*
A low-loss header offers additional
benefits not provided by a pair of
closely spaced tees. Viessmann strongly
recommends and prefers the use of a
low-loss header over closely spaced tees.
Please see page 13 for details.