Download Print this page

Delta DOP-107EG Instruction Sheet page 2

Hide thumbs Also See for DOP-107EG:

Advertisement

(6) Hardware specifications
Model
DOP-107EG
Panel type
7" TFT LCD (65535 colors)
Resolution
800 x 600 pixels
Display
Backlight
LED backlight (half-life under room temperature 25
141.00 x 105.75 mm
Display range
Brightness
450 cd/m² (Typ.)
CPU
ARM Cortex-A8 (800 MHz)
Flash ROM
256 Mbytes
RAM
256 Mbytes
Touchscreen
4-wire resistive touchscreen > 10,000,000 operated
Multi-tone frequency (2 K – 4 KHz) / 80 dB
Buzzer
Network interface
10/100 Mbps Auto sensing (with built-in isolated power circuit)
USB
1 USB slave Ver 2.0; 1 USB host Ver 2.0
SD
COM1
RS-232 (supporting flow control)
Serial
communication
COM2
RS-232 (supporting flow control) / RS-485
port
COM3
RS-422 / RS-485
Auxiliary function key
Calendar
Cooling method
Natural cooling
CE / UL (please use shielding network cable and magnetic ring with the
Approvals
filter of 300 ohm / 100 MHz)
Panel waterproof level
IP65 / NEMA4
DC +24 V (-15% to +15%) (please use an isolated power supply)
*2
Supplied by Class 2 or SELV circuit (isolated from MAINS
Operation voltage
by double insulation)
Leakage current
500 VAC for 1 minute (between DC24V terminal and FG terminal)
Power consumption
*2
8.4 W (Max)
Backup battery
3V lithium battery CR2032 × 1
About 3 years or more at 25
Backup battery life
(subject to operation temperature and condition)
Operation temperature
0
o
C to 50
Storage temperature
-20
o
C to +60
10% to 90% RH [0
o
C to 40
Operating environment
pollution degree: 2
Conforms to IEC61131-2: continuous vibration 5 Hz - 8.3 Hz with amplitude
Vibration resistance
3.5 mm; 8.3 Hz - 150 Hz with amplitude 1G
Conforms to IEC60068-2-27: 11 ms, 15 G Peak,
Shock resistance
in X, Y, Z directions each for 6 times
Dimension
184 x 144 x 50
(W) x (H) x (D) mm
Mounting dimension
172.4 x 132.4
(W) x (H) mm
Weight
Approx. 800 g
Note:
1. The half-life of the back light is defined as the maximum luminance being reduced by 50% when the
maximum drive current is supplied to the HMI. The life of LED backlight shown here is estimated at the
room temperature of 25
o
C with ambient humidity.
2. The withstand voltage of the isolated power circuit is 1500 V peak for 1 minute.
3. The HMI power consumption is the power consumed when the HMI is not connecting with other
peripheral devices. To ensure normal operation of the HMI, the recommended capacity of the power
supply is 1.5 to 2 times of the specified power consumption.
4. Isolated power supply is recommended.
5. For DOPSoft programming software for DOP-100 series and the user manual, you can download them
at http://www.delta.com.tw/ia.
6. DOP-100 series can be used with other industrial automation equipment. Please read through this
sheet carefully and install the product according to the instructions to avoid danger.
o
C > 20,000 hours)
*1
*2
SD * 1
*2
*2
*2
N/A
Built-in
*3
o
C
o
C (32
o
F to 122
o
F)
o
C (-4
o
F to 140
o
F)
o
C], 10% to 55% RH [41
o
C to 50
o
C];