Viessmann VITODENS 100-W Installation And Service Instructions Manual page 49

For contractors. wall mounted gas condensing boiler natural gas and lpg version
Hide thumbs Also See for VITODENS 100-W:
Table of Contents

Advertisement

Repairs
(cont.)
20
10
8
6
4
2
1
0.8
0.6
0.4
10 30 50 70 90 110
Temperature in °C
Replacing flow limiter (gas condensing combi boiler)
A
B
C
Serial no.
(Type plate)
7441748
7441749
3. Replace the sensor in the case of
severe deviation.
1. Drain the boiler from the DHW side.
2. Pivot the control unit downwards.
3. Undo screws A.
4. Remove the cap B.
5. Remove faulty flow limiter C.
6. Select new flow limiter C corre-
sponding to boiler serial no. (see type
plate) and the following table.
7. Insert new flow limiter C.
8. Fit new cap B provided.
Flow rate
l/min
Troubleshooting
Colour
12
14
brown
red
49

Advertisement

Table of Contents
loading

Table of Contents