Parameters - ABB ACS 400 User Manual

N2 protocol
Hide thumbs Also See for ACS 400:
Table of Contents

Advertisement

Parameters

Table A-1 I/O point list
Numb
1
OUTPUT FRE-
2
RATED SPEED
3
4
CURRENT
5
RATED TORQUE
6
RATED POWER
7
DRIVE TEMPERA-
8
KILOWATT
9
MEGAWATT
10
RUN TIME
11
DC BUS VOLT-
12
PID-CTRL ACT
13
LAST FAULT
14
PREV FAULT
15
OLDEST FAULT
16
AI 1 ACTUAL
17
AI 2 ACTUAL
18
AO 1 ACTUAL
1
STOP/RUN
2
FORWARD/
3
OK/FAULT
4
RELAY OUTPUT 1
5
RELAY OUTPUT 2
6
DIGITAL INPUT 1
7
DIGITAL INPUT 2
A-2
Point
Analog Inputs:
SPEED
Binary Inputs:
ACS/ACH 400 Direct N2 Bus Interface
Units
Hz
%
rpm
A
%
kW
°
C
kWh
MWh
h
V
%
%
%
mA
0 = Stop, 1 = Drive Run-
0 = Forward, 1 = Reverse
0 = OK, 1 = Drive Faulted
Range
0 - 250
0 – 100
0 – 9999
0 – 9999
-300 – 300
0 -9999
0 – 125
0 – 9999
0 – 999
0 – 9999
0 – 999
0 – 100
fault code
fault code
fault code
0 - 100
0 - 100
0 - 20
0 = off, 1 = on
0 = off, 1 = on
0 = off, 1 = on
0 = off, 1 = on