Binary Output; Communication Setup - ABB ACS 400 User Manual

N2 protocol
Hide thumbs Also See for ACS 400:
Table of Contents

Advertisement

Binary Output

Communication
Setup
Parameter
1 OEM Applica-
tion ID and
Revision
2 Drive ID-num-
ber
3 Communication
time-out time
4 Communication
fault function
5 Good Message
Counter
6 Bad Message
Counter
ACS/ACH 400 Direct N2 Bus Interface
The binary output points support the following
features:
Binary Output value
Override value is used to change the
Binary Output value. It is not possible to
return to the previous value by removing
the override. The override feature is
used only to change the value.
To activate the direct N2 Bus connection, set
parameter 5005 PROTOCOL SEL to OEM
APPLIC (4). If you can not see this selection on
the panel, your drive does not have N2 protocol
software in the application memory.
For the direct N2 Bus communication there are
new setup parameters on the drive. These are
located in the group 53 OEM APPLICATION.
These parameters are shown in Table 4-1
"Group 53 OEM APPLICATION".
Table 4-1 Group 53 OEM APPLICATION
Panel Text
5301 OEM
APP PAR1
5302 OEM
APP PAR2
5303 OEM
APP PAR3
5304 OEM
APP PAR4
5305 OEM
APP PAR5
5306 OEM
APP PAR6
Chapter 4 – Programming
Range/
Description
Unit
1010 -
N2 Software ID and
1099
revision
1 - 255
Drive N2 address
1 – 600
Time limit for
(1.0 -
communication loss
60.0 s)
detection
0 – 3
Operation in case
communication with
master device is lost
0 –
Rolling counter for
65535
good messages
0 –
Communication error
65535
counter
4-3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ach 400

Table of Contents