Connecting Pipes And Fittings - Siemens FDA241 Planning, Mounting

Asd pipe system
Hide thumbs Also See for FDA241:
Table of Contents

Advertisement

Mounting/Installation
5
Installing the pipe system

5.2.2 Connecting pipes and fittings

50 | 56
Building Technologies
Fire Safety
WARNING
Easily inflammable solvents in the adhesive
Risk of fire upon contact with naked flames or hot surfaces
Smoking, fire and naked flames are prohibited when working with adhesive!
Ensure the room in which the adhesive is being used is well ventilated.
Use a clean brush to apply the adhesive. Do not apply different adhesives with
the same brush.
The pipes are trimmed to the desired length.
The required fittings, e.g. pipe connections, T-pieces and bends, are available.
Suitable adhesive is available for gluing pipes and fittings.
Pipes and fittings are connected in a dry room.
1. Press the pipe to the fitting as far as the stop.
2. Draw a line on the pipe along the flange of the fitting to mark the pressed-in
part of the pipe.
3. Pull the pipe out of the fitting.
4.
WARNING! Health risk when handling adhesive. Observe the instructions
for use and the safety data sheet for the adhesive!
5. Apply the adhesive to the marked area on the end of the pipe. The marked
area must be completely and evenly covered with adhesive.
6. Slide the pipe into the fitting.
7. Press the pipe and fitting together for at least 30 s.
8. Remove the residual adhesive from the pipe with a cloth.
9. Repeat the steps described for every fitting.
10. Wait until the adhesive has dried.
The connected pipes and fittings can be installed on the wall or ceiling.