Commissioning and service field (ISF)

Pos: 16.2 /Überschriften/1.1/1-spaltig/S - U/Typische Inbetriebnahme mit dem Servicefeld (ISF) @ 7\mod_1167725302531_3101.doc @ 53720
7.1

Typical commissioning with the service field (ISF)

Pos: 16.3 /Konfiguration, Parametrierung/Aktorik/Antriebe/Leistungselektroniken/EBS852, EBS862/Typische Inbetriebnahme mit dem Servicefeld (ISF) EX @ 20\mod_1211783475296_3101.doc @ 195998
Important
The operating range of the actuator is not factory-set. To set the actuator's operating range,
set the write protection switch to "OFF". Once commissioning is complete, set the write
protection switch to "ON".
For information about setting up the mechanical end stops, refer to the operating instructions
for the relevant actuator.
Danger – Serious damage to health / risk to life
Make sure that the actuator can move without posing a risk.
7.1.1

Status

The electronic unit is connected to the power supply and wired to the actuator.
Move the write protection switch (6) to the "OFF" position.
The electronic unit is in "MAN" mode; no signal at digital input 1 (DI 1).
No error (if an error is pending, the LEDs will flash alternately at 4 Hz).
7.1.2

"Device setup" operating mode

1. Switch the electronic unit to "Device setup" mode. Press and hold down both travel buttons
(9) at the same time for approx. 5 s until both LEDs (items 5 and 10 in Fig. 21) flash in sync
at a rate of 4 Hz.
Important
Once commissioning is complete, set the write protection switch to "ON".
7.1.3

Setup via user interface

Context-sensitive online help can be called at any time via the graphical user interface.
Important
The RS232 communication cable provides a conductive ground connection between the
computer and the Contrac electronic unit. If the PC is grounded, a ground loop may form in the
system.
42/68-831-EN
Commissioning and service field (ISF)
EBS852, EBS862 (Contrac)
29