Commissioning
7.1 Prior to commissioning
Electrical connection
● The grounding and equipotential bonding connections have been made correctly.
● The machine is connected so that it rotates in the direction specified.
● Appropriately configured control and speed monitoring functions ensure that the motor
● The minimum insulation resistance values are within tolerance.
● Minimum air clearances have been maintained.
● Any supplementary motor monitoring devices and equipment have been correctly
● The values for "Alarm" and "Shut down" at the monitoring equipment are set to the values
● All brakes and backstops are operating correctly.
Switching overvoltages
When high-voltage machines with starting current I
after they have been blocked, then in individual cases inadmissibly high switching overvoltages
for the stator winding insulation can occur through multiple restrikes.
The peak voltages which arise as a result can damage the winding insulation.
● If you are using vacuum circuit breakers and vacuum contactors, use an appropriate surge
● An additional RC arrester (resistor and capacitor connected in series) makes sense at
See also
Switching high-voltage motors (Page 26)
Converter operation
● If the design of the motor requires connection to a particular converter type, the rating plate
● The converter is correctly parameterized. The parameterization data is specified on the
● Any supplementary motor monitoring devices and equipment have been correctly
● In continuous operation, the motor cannot exceed the specified upper speed limit n
● The bearing insulation should be implemented as shown on the plates.
72
cannot exceed the permissible speeds specified in the technical data. See also the system-
specific documentation.
connected and are fully functional. Refer to the "Technical data and drawings" section for
more information.
listed in the "Explanatory text for the machine dimension drawing" section.
suppressor, such as the Siemens 3EF (zinc oxide varistor with spark gap).
unfavorable operating points/under unfavorable line supply conditions.
will contain corresponding additional information.
rating plate of the machine. Information about the parameters is available in the operating
instructions for the converter.
connected and are functioning correctly.
undershoot the lower speed limit n
The permissible acceleration time to the limit speed n
assignment.
≤ 600 A are switched off while starting or
A
.
min
depends on the parameter
min
SIMOTICS HV M 1RN76308PR900CG0-Z
or
max
Operating Instructions 07/2018