*Approximately 95 CFM with optional power vent kit. Actual vent CFM performance will vary due to application and installation conditions.
NTP07A**A3A
1&3
Voltage
230/208
Capacity (BUTH)
7,000/6,800
Amps
2.8/3.0
Watts
655/635
EER
UNIT WITHOUT
ELECTRIC HEATER
2&4
Minimum Circuit Ampacity
CFM
HIGH
245/240
LOW
220/205
HIGH
265/260
LOW
230/215
FAN ONLY*
COMPRESSOR & FAN*
Dehumidification
(pints/hr)
Net Weight
Shipping Weight (approx.
lbs.)
NOTES:
1. All 265V models must use Amana
®
brand's subbase (PTSB4**D) or an Amana
2. Minimum branch circuit ampacity ratings conform to the National Electric Code. However, local codes should apply.
3. Minimum voltage on 230/208 volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 238.5 volts; maximum is 291.5 volts.
4. Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-style time delay fuses (included
®
and factory installed on Amana
brand all 265 volt chassis).
5. Heating capacity and efficiency are based on unit operation without condensate pump. Unit automatically switches to electric heat at approximately 24°F outdoor ambient.
6. Total watts for 12,000 and 15,000 Btuh models. Subtract 70 watts for PT07/09*B*AE.
7. Please specify 2-digit heater kW size to complete model number.
9. Refrigerant used in all systems is R-22.
8. Total amps for 12,000 and 15,000 Btuh models; subtract 0.2 amps for PT07/09*B*AE.
10. All units meet or exceed ASHRAE 90.1 standards..