Samsung DVM S ECO BIG Series Service Manual page 91

System air conditioner
Table of Contents

Advertisement

■ EVI (ESC) EEV leakage or internal leakage of intercooler or incorrect connector insertion of
EVI (ESC) EEV. (E-438) (cont.)
Outdoor unit Display
Indoor unit Display
Judgement Method
Cause of problem
Samsung Electronics
Duct, Cassette (1 / 2Way), Console, Ceiling
Operation
×
Cassette (4Way / Mini 4Way)
Operation
×
Duct, Cassette (1/2 Way), Console, Ceiling
Operation
×
• DSH <10 °C, EVI Out-in <= 0°C & frequency> 65Hz 40 minutes maintaining
• EVI EEV and Intercooler leakage, excessive refrigerant amount, Outdoor
Check Valve inserted opposite.
• I ndoor Unit EEV leakage, direct connection between Indoor Liquid Pipe and
the Gas Pipe.
E-438
Defrost
Timer
×
Defrost
Timer
Timer
Turbo
×
※ ●
: ON
: Flash ×: OFF
Troubleshooting
Fan
Filter / MPI
Filter
24°C
27°C
4-49