Troubleshooting
■ Outdoor unit's option switch setting error (Using E2P option of other models or emergency
operation for compressor malfunction option setting was enabled on all compressors of
corresponding outdoor unit). (E-560)
Outdoor unit Display
Judgement Method
Cause of problem
Is the Compressor
breakdown
setting value is "not set"?
Is the outdoor unit
EEPROM accurately
connected to
connector?
Download relevant model
EEPROM and then reset.
※ Execute automatic commissioning for UP
cancellation after EEPROM download.
4-60
• Refer the next page.
• Option setting error of outdoor unit.
(E2P option use of other model or set of the relevant outdoor unit, compressor
breakdown)
Yes
Yes
E-560
Set the compressor breakdown setting value as
No
"not set"
※ When setting breakdown for repair and replace
of compressor : Change the setting after replace.
No
Connect outdoor unit EEPROM and then reset.