Baxi Ecogen 24/1.0 Installation & Servicing Instructions Manual page 32

Gas fired wall mounted condensing boiler and power generator
Table of Contents

Advertisement

Fig. 21L
Fig. 21m
page 31
15. For aesthetic purposes it is permissible to route the 60Ø exhaust in an enclosed box, but the air inlet and plume outlet MUST remain in free air.
16. It is also possible to separate the plume outlet from the 93° elbow to allow the flue to be installed as shown in Fig. 21n.
17. To do this, first slacken the two screws retaining the plume outlet to the elbow, and remove the outlet (Fig. 21p). The elbow can now be used to connect the vertical to
horizontal 60Ø exhaust (Fig. 21n). Retighten the screws in the elbow.
18. The outlet can now be fitted into the female end of an 60Ø extension piece. It must be secured using two of the screws supplied in the bag with the 'Jubilee' clip.
19. Mark the female end of the extension at 30mm as shown in two positions, directly opposite each other (Fig. 21q).
20. Using a suitable bit (e.g. 2mm), drill through the extension and outlet. Secure using two of the screws supplied.
21. The remaining screw must be used to secure the adaptor to the concentric terminal.
22. When the plume outlet is positioned under a balcony or other projection (Fig. 21r) it must protrude at least 200mm (it is not necessary to extend it further than this).
23. When under balconies or projections it is permissible to rotate the concentric flue length up to 70°, clockwise or anticlockwise (Fig. 21s), if there is insufficient space to
connect vertically.
24. This will allow the connection of the exhaust to the outlet spigot.
25. All other minimum & maximum dimensions must be adhered to, and the air inlet positioned such that it will not be subject to rain entry.
Fig. 21n
Fig. 21p
Fig. 21q
Fig. 21r

Advertisement

Table of Contents
loading

Table of Contents