Technical Specifications; Troubleshooting - STEINEL IR 180 UP easy Manual

Hide thumbs Also See for IR 180 UP easy:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 11
10� Technical specifications
Dimensions (H × W × D)
Power supply
Power consumption
Output
Incandescent / halogen lamp load
Fluorescent lamps, electronic ballast
Fluorescent lamps, uncorrected
Fluorescent lamps, series-corrected
Low-voltage halogen lamps
LED < 2 W
2 W < LED < 8 W
LED > 8 W
Capacitive load
Minimum connected load
Mounting height
Sensor system
Angle of coverage
Reach
Twilight setting
Time setting
Temperature
IP rating
81 × 81 × 57 mm
220 - 240 V, 50 / 60 Hz
25 mW
200 W
150 W
150 VA
150 VA
200 VA
40 W
100 W
160 W
132 µF
with N: 1 W
without N: 4 W
1.1 m
Passive infrared
180° with 90° angle of aperture
max. 8 m tangential
2 - 1000 lux
5 sec - 30 min
0°C to +40°C
IP20
- 26 -
11� Troubleshooting
Malfunction
Cause
Sensor switch without
■ Fuse has tripped, not
voltage
switched ON
■ Short circuit
Sensor switch not
■ Lamp faulty
switching ON
Sensor switch not
■ Twilight setting in night-
switching ON
time mode during
daytime operation
■ Fuse has tripped
Sensor switch not
■ Continued movement
switching OFF
within the detection zone
■ Light is in detection zone
and keeps switching ON
as a result of
temperature change
■ Other sensor switch is
connected in parallel and
still active
Sensor switch always
■ Light being operated in
switches ON/OFF
the detection zone
■ Animals moving in
detection zone
LEDs glowing, flickering ■ LEDs responding too
sensitively
Remedy
■ Activate, change fuse,
turn ON mains switch,
check wiring with voltage
tester
■ Check connections
■ replace lamp
■ Reset
■ Activate, change fuse,
check connection if
necessary
■ Check detection zone
■ Check detection zone
■ Wait for time setting of
the other sensor switch
to elapse
■ Check detection zone
■ Check detection zone
■ Connect neutral
conductor (N), change
lamp
- 27 -

Advertisement

Table of Contents
loading

Table of Contents