Automatic transfer switching devices for safety power supplies
Hide thumbs Also See for ATICS DIO Series:

Advertisement

Quick Links

Quick start "Installation and connection"
ATICS-...-DIO Quick start
Automatic transfer switching devices for safety power supplies
Software-Version: D333 V1.2x, D334 V1.2x, D335 V1.0x
This reference guide does not replace the operating manual. You will find the operating manual in the download area of our homepage. Make sure
that the personnel has read this manual and understood all instructions relating to safety.
1. Safety instructions
Danger: Risk of fatal injury from electric shock
Parts of the system are live. During installation and connection:
Do not touch parts of the system.
Make sure that the power supply has been disconnected and the
system is dead.
Switch the ATICS® to manual mode and to switch position "0".
Lock the changeover device with a padlock to prevent it starting
accidently.
Warning: Risk of destruction if mains voltage incorrect
The permissible mains voltage is indicated on the nameplate.
2. Scope of delivery
ATICS® transfer switching device
• including connectors, bridge and terminal covers
• Measuring current transformer STW3 resp. STW4
Documentation
• You can find the ATICS® manual and the manuals of other sys-
tem components under:
http://www.bender.de > Service & support >
Download > Operating manuals
• Quick reference guides and checklist
4. Device overview
1
12
11
10
ATICS-DIO_D00080_02_Q_XXEN/04.2017
2
3
4
9
8
Danger: Risk of fatal injury from electric shock
Connecting wires can come loose and fall out if the ferrules being used
are too short, the wire ends are tinned or the connection screws have
not been tightened enough.
Consider a stripping length of 20 mm and do not use ferrules
when connecting lines 1, 2 and 3 (ATICS-4-160A-DIO only: strip-
ping length 15 mm, with or without ferrules).
Use a torque wrench to tighten the terminal screws. Check all
the screws on a regular basis to make sure they are seated
tightly.
ATICS-4-125A-DIO and ATICS-4-160A-DIO only:
High temperatures may affect the terminals
The terminals for the connection of Line, 1, 2, 3 are designed for the
specified rated operational current, at room temperature.
Avoid higher temperatures or ensure that the load current is
reduced.
3. Other system components required
• Alarm indicator and test combination MK... or/and alarm indi-
cator and operator panel TM...
• Bypass switch (recommended for ATICS-2-DIO)
• For screw mounting only: mounting screws M5
Transfer switching device ATICS-2-DIO
1.
Green plug connector for line 1 and line 2
2.
Control buttons
3.
Inspection window for switch position
4.
Selector switch for manual mode selection, also shows the
switch position.
5.
Allen key for manual mode
6.
Transparent cover for changeover switch (manual mode), seal-
able
7.
Wiring diagram for lines 1, 2 and 3
5
8.
Three coded connector plugs
9.
Locking device for switch position 0
6
10. Green plug connector for line 3
11. LCD
12. Operating and alarm LEDs
7
1

Advertisement

Table of Contents
loading

Summary of Contents for Bender ATICS DIO Series

  • Page 1 • For screw mounting only: mounting screws M5 Documentation • You can find the ATICS® manual and the manuals of other sys- tem components under: http://www.bender.de > Service & support > Download > Operating manuals • Quick reference guides and checklist 4. Device overview...
  • Page 2: Tools Required

    ATICS-…-DIO Quick start Transfer switching device ATICS-4-DIO Green plug connector for line 1 Green plug connector for line 2 Control buttons Inspection window for switch position Selector switch for manual mode selection, also shows the switch position. Allen key for manual mode Transparent cover for changeover switch (manual mode), seal- able Wiring diagram for lines 1, 2 and 3...
  • Page 3: Removing The Terminal Covers

    ATICS-…-DIO Quick start Removing the terminal covers Push back the locking hook (B) in the middle of the top and bottom terminal cover (A) by using a screwdriver. Remove the terminal cover. Mounting the ATICS® on DIN rail Place the ATICS® on the top edge of the rail. ATICS-2-DIO: Use a screwdriver to pull down the lower yellow slide lock (C) and snap the ATICS®...
  • Page 4: Mounting The Atics® On Mounting Plate

    ATICS-…-DIO Quick start Mounting the ATICS® on mounting plate Warning: Screw heads or washers reduce voltage clearance Provide for sufficient clearance to live conductors (voltage clearance) by using mounting screws with flat screw heads and flat washers. If mounted on electrically conductive material: the mounting plate has to be earthed and the area under the terminals has to be covered with insulating material.
  • Page 5: Wiring Diagrams

    ATICS-…-DIO Quick start 11. Wiring diagrams Connection ATICS-2-DIO Terminal Meaning Connection line 1 (input line) L,N Connection line 2 (input line) L,N Connection line 3 (output line) N,L l, k Connection measuring current transformer STW3 (T3) for monitoring the load current downstream the transfer switching device (short-circuit monitoring) GND, En/Ex Connection must not be used.
  • Page 6 All rights reserved. Reprinting and duplicating only with Genehmigung des Herausgebers. Änderungen vorbehalten! permission of the publisher. Subject to change! © © Bender GmbH & Co. KG Bender GmbH & Co. KG Fotos: Bender Archiv. Photos: Bender archives. Bender GmbH & Co. KG P.O.
  • Page 7: Safety Instructions

    Quick start "Commissioning and operation" ATICS-…-DIO Quick start Automatic transfer switching devices for safety power supplies Software version: D333 V1.2x/D334 V1.2x/D335 V1.0x This reference guide does not replace the operating manual. You will find the operating manual in the download area of our homepage. Make sure that the personnel has read this manual and understood all instructions relating to safety.
  • Page 8: Enabling Automatic Mode

    ATICS-…-DIO Quick start 6. Enabling automatic mode ► In order to enable automatic mode, close the transparent cover of the automatic transfer switching device and seal it, if necessary. 7. Display in error-free operation There is no alarm message. Standard display ATICS-2-DIO: Pos.
  • Page 9: Menu Mode: Operation And Setting

    Format, date and time setting 10. Password Enable resp. set password for settings and test 11. Service Reserved for settings to be made by authorised Bender Serv- ice personnel. 5. Control Run TEST and RESET for this device 1. TEST Changeover, last changeover saved as a test, generator 2.
  • Page 10: Troubleshooting