Table 6—Specifications for MagneW 3000 PLUS , continued
Outputs (Transmitter)
Display
Operator Interface
Mounting
20
Design (continued)
• Detector's coil excitation current
• Current output without SFC communications requirement: 4 to 20 mA dc into a 0 to 600 ohms
load with external 24 Vdc power supply.
• Current output with SFC/DE communications requirement: 4 to 20 mA dc into a 250 to 1460
ohms load with an external 24 Vdc power supply.
• Contact output: For a maximum external load of 30 Vdc/200 mA, indicating any one of the
following condition states:
– Alarm actuating contacts for
Self-diagnosis alarm —Outputs an alarm-actuating contact when the self-diagnosis function
detects an error.
No-load detection alarm (with empty-status detection) —Outputs an alarm-actuating
contact when the fluid level in the detector goes below the electrode level.
Upper/lower flow limit value alarm —Outputs an alarm-actuating contact when the flow
volume exceeds the upper/lower limit values.
Two-stage flow value alarm (with two contact outputs) —Outputs an alarm-actuating contact
when the flow value exceeds the two upper limits (H and HH) or the two lower limits (L and
LL).
– Range identification output—Outputs a contact for large and small ranges, forward and
reverse direction ranges.
– Counter preset status (for pulse output model)—Outputs a contact when the built-in
counter reaches the preset value.
Display card can rotate 90° for installation on vertical pipe.
Backlit liquid crystal display (LCD).
Display board:
One line with six 7-segmented digits—Main display
Dot matrix, two lines with 16 columns—Auxiliary display
Display contents:
• instantaneous flow rate in percent
• instantaneous actual flow rate in a variety of engineering units
• total volume (with pulse output model)
• engineering data
Four infrared touch sensor keys OR
Hand-held communicator with keyboard and LCD. Connects anywhere in the 4-20 mA output line.
Converter:
• Integral mounts directly on detector
• Remote mounts on wall or 2-inch pipe
Detector: A variety of piping connections are offered–flange, wafer, hose, sanitary coupling, etc.
MagneW 3000 PLUS Specification and Application Guide
Supply voltage 8.5
Load Resistance (Ω) =
1460
620
Operating
Range
300
250
16.0
Supply Voltage (Vdc)
0.025
24.0
45