Pump Maintenance - Pentair Pool Products HYDROMATIC S4BX Installation And Service Manual

Submersible pump with hazardous location motor end
Table of Contents

Advertisement

Pump
Maintenance
NOTE: Any unauthorized field
repair voids the warranty, the
hazardous location rating, and
Factory Mutual approval.
As the motors are oil filled, no
lubrication or other maintenance
is required.
If the heat sensor and seal failure
are hooked up properly, no
attention is necessary as long
as the seal failure indicator
light doesn't come on. To ensure
continuity of the seal sensor
leads, a test light is provided on
intrinsically safe Hydromatic
panels as standard equipment.
Pump should be checked every
quarter for corrosion and wear.
Servicing instructions:
iMPOrTANT:
read
directions before replacing any
parts.
WArNiNg: Before handling
these pumps and controls, always
disconnect the power first.
Do not smoke or use sparkable
electrical devices or flames in a
septic (gaseous) or possible
septic sump.
Field Service on Hydromatic
Hazardous Location Pumps:
If a Hydromatic
location pump is used in a
hazardous location, or if the pump
is still in warranty, the pump must
be returned to the factory for
service
or
repaired
authorized
Factory
Hydromatic
service
6
Charges will not be allowed if (in
warranty) the pump is taken to a
motor repair shop that is not an
authorized
Hydromatic service center. This
will ensure the integrity of the
hazardous location rating of the
pump and comply with our
warranty requirements. Pumps out
of warranty and not used in a
hazardous location can be field
serviced
serviceman. When any field
servicing is performed on a pump,
the following instructions should
be followed carefully.
Disconnecting Pump Cords:
If a Hydromatic
location pump is to be removed
from its location, one of two ways
may be used to disconnect the
pump cords from the rest of the
system.
Pump cords may be disconnected
at control panel (on sump mounted
control panels) and cord assembly
taken with pump.
all
CAUTiON: if cord openings
from sump to control panel are
open, gases from sump could
enter panel and an explosive
condition could exist.
Pump cords may be disconnected
at pump by removing the cord and
cap assembly, unplugging sensor
wires, and removing wire nuts.
After removal from pump, reinstall
wire nuts in cord and cap assembly.
hazardous
CAUTiON: Do not reconnect
power to a cord and cap assembly
while removing from pump.
replacing Cords:
in
an
The power cord and heat sensor -
Mutual
center.
seal failure cord is potted into the
Factory
Mutual
by
any
reputable
hazardous
connection box cap, forming the
cord and cap assembly.
If cords require replacement due
to damage or cords being too
short, cord and cap assembly must
be replaced as a complete assembly
available from factory.
1. Remove cord and cap assembly
from connection box.
2. Disconnect wires taking note
of color/number coding.
3. Connect wires of new cord and
cap assembly in same manner
as the old one was removed.
4. Check for moisture and dryout.
5. Reinstall cord and cap assembly
on connection box taking care
not to pinch wires.
6. Check
pump
for
rotation before returning to
normal service.
replacing Stator:
If motor winding is burned or
shorted, it can be rewound or
replaced with new factory wound
stator. Refer to sectional drawing
of pump and motor, and use the
following steps to remove and
replace stator.
1. If only the stator is damaged,
it may not be necessary to
completely dismantle pump as
stator and housing can be lifted
from pump without disturbing
seals or bearings.
2. Drain all oil from upper
housing. Remove drain plug
in bottom of bearing housing,
and remove connection box to
allow air to enter.
3. When connection box is lifted
off, connection wires to motor
will be exposed. These wires
are tagged with a metal
marker giving wire number.
Disconnect wires and remove
connection box.
proper