Connecting The Power Cables; Connection Diagram - ABB ACS880-34 Hardware Manual

Drive modules (132 to 400 kw, 200 to 450 hp)
Hide thumbs Also See for ACS880-34:
Table of Contents

Advertisement

Connecting the power cables

Connection diagram

ACS880-34
1
For alternatives, see section
example of this chapter, the disconnecting device is not in the same cubicle with the drive module.
2
If a shielded cable is used (not required but recommended) and the conductivity of the shield is
< 50% of the conductivity of the phase conductor, use a separate PE cable (2a) or a cable with a
grounding conductor (2b).
3
We recommend 360-degree grounding at the cabinet entry if a shielded cable is used. Ground the
other end of the input cable shield or PE conductor at the distribution board.
4
Input and output power cabling panels (option +H381)
5
We recommend 360-degree grounding at the cabinet entry, see page
6
Use a separate grounding cable if the conductivity of the cable shield is < 50% of the conductivity of
the phase conductor and there is no symmetrically constructed grounding conductor in the cable
(see page 65).
Installation example with full cabling panels (option +H381) 141
L2
L3
L1
L1
L2
L3
3
4
L1/U1 L2/V1 L3/W1
UDC-
L1/U1 L2/V1 L3/W1
UDC-
INPUT
OUTPUT
T1/U2 T2/V2 T3/W2
7
4
T1/U2 T2/V2 T3/W2
8
5
V1
W1
U1
~
3
Motor
Selecting the supply disconnecting device
(PE)
PE
(PE)
1
2b
2a
UDC+
UDC+
PE
6
on page
49.
9
58.
In the installing

Advertisement