Commissioning - Chamberlain GAROG TST-2 Operational Description

Door control device
Table of Contents

Advertisement

Operational Description TST WS-B
6

Commissioning

The following introduction serves as directions for checking and setting door installations with mechanical end
switches and contains some important observations which are to be considered. Familiarisation with the preceding
chapter is a requirement.
NB: When changing security strip systems, switch off the control device and after connection of the new system, set
to setting operation (DIP1=On). For use of pneumatic strip (pressure switch) DIP-switch 6 has to be in the
testing mode (DIP6=ON)
1. Check the electrical connections according to the connection configuration plan, the door mechanism and the
desired installation configuration including the associated DIP switches and plug-in modules so that no
mechanical or electrical risk can arise from any of the components.
2. Check the power connection at site for right rotary field of the 3 phases
3. Bring the door into the middle position with the control device switched off and set the mechanical end switches
in such a way that no switch is actuated.
4. Switch DIP switch S1 to "OFF". The control device works in dead man operation after being switched on, ie. the
drive runs only as long as the OPEN or CLOSE button of the membrane keypad is actuated. NB: The door
moves in this type of operation without consideration of the security devices (light barriers, security
strip, draw-in security device)
5. Plug in mains power plug or switch on the power supply.
6. Use the CLOSE button to move the door close to the closed position. NB: with doors of unknown slow-down
travel, leave sufficient spacing from the end position.
7. If the door turns in the wrong direction: incorrect motor rotary field, shut off the power and exchange two motor
connections.
8. Set the lower end switch such that it is just actuated. Then adjust the end switches more precisely as required,
by further movements into this end position.
NB: End switches must not be passed over in the end positions.
9. Set lower security end switch. Observe the setting requirements of the drive manufacturer.
10. Use OPEN button to move the door close to the open position.
11. Set upper end switch such that it is just actuated. Then adjust the end switches more precisely as required, by
further movements into this end position. NB: End switches must not be passed over in the end positions.
12. Set upper security end switch. Observe the setting requirements of the drive manufacturer.
13. Intermediate holding (if required): Move door into the desired intermediate holding position.
14. Set intermediate holding switch such that it is just actuated (considered from opening travel direction)
15. Adjustment of pre-end switch:
The pre-end switch is used for a switch –off of the reversal function when security strip is actuated. It must be
adjusted relating to the door type shown in the figure below. The gap between the actuation point of the security
strip and the floor should max. 50 or 20mm.
DIP 7:OFF
Switch off reversal
max. 50 mm
16. Set pre-end switch in such a way that during closing travel it is just actuated at this position.
17. Check and if necessary correct the end switch positions by dead man opening and closing travel.
18. Switch off control device and switch DIP switch S1 to "ON". The control device is in automatic operation when
switched on again.
19. Check operation of all security devices such as closing edge security device, light barriers, emergency stop
etc.
Wsb_bse8.doc
DIP 7: ON
Ignore security strip actuation
max. 20 mm
mt 041102
Page: 7