Carrier 48FC Series Controls, Start-Up, Operation And Troubleshooting page 105

Single package rooftop units with systemvu controls version 1.x and puronr (r-410a) refrigerant
Hide thumbs Also See for 48FC Series:
Table of Contents

Advertisement

TABLE
DISPLAY NAME
OCC_DIAG
Currently Occupied
Active Occupancy control
0 = 24/7 OCC
1 = Schedule
2 = BAS CTRL
3 = REMOC CTL
4 = Time Override
5 = Linkage
6 = Forced
Linkage Occupied Request
Timed Override Hours
Remote Occupancy Switch
BMS Occupancy Request
0 = Unoccupied
1 = Occupied
2 = Disabled
Local Sched Occ Request
0 = Unoccupied
1 = Occupied
Active Schedule period
Mins until next occupied
BACnetCal Object Status
Today Is A Holiday
Tomorrow Is A Holiday
Next Occupied Day
Next Occupied Time
Next Unoccupied Day
Next Unoccupied Time
Previous Unoccupied Day
Previous Unoccupied Time
Accept Global Holidays?
Global Schedule Broadcst
CCN Schedule Number
0
= Always Occupied
1--- 64 = Local Schedule
65--- 99 = Global Schedule
Remote Occupancy Channel
Remote Occupancy Switch
Timed Override Duration
BAS Protocol Select
HW_IO
0 = None
1 = IAQ
2 = OARH
3 = RARH
4 = OAQ
5 = SPRH
6 = OACFM
Assigned AI06 Function
Assigned AI07 Function
Assigned AI08 Function
APPENDIX D: SystemVut Controller CCN Tables
Maintenance Tables (cont)
Yes/No
0 to 6
0=Unocc,
1=Occupied,
2=Disabled
0 to 240
On/Off
0 to 2
0 to 1
0 to 8
--- 1 to 10080
Yes/No
Yes/No
DDD
hh:mm
DDD
hh:mm
DDD
hh:mm
Yes/No
Yes/No
0 to 99
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB Y3
On/Off
0 to 4
0=NONE,
1=CCN,
2=BACNET
0 to 6
0 to 6
0 to 6
VALUES
UNITS
min
min
min
min
min
hrs
105
POINT NAME
WRITE STATUS
OCCUPIED
Forcible
OCC_CTRL
LNK_OCC
Forcible
OVR_EXT
Forcible
REMOCC
Forcible
BMS_OCC
Forcible
LOC_OCC
Forcible
PER_NO
MINTILOC
CALOBJST
HOLTODAY
HOL_TMRW
NXTOCDAY
NXTOCTIM
NXTUNDAY
NXTUNTIM
PRVUNDAY
PRVUNTIM
blank
HOLIDAYT
CCN_GSBC
SCHEDNUM
RMOCCHAN
REMOCC
Forcible
OTL_CFG
BMS_CFG
MBBAI06F
MBBAI07F
MBBAI08F