Download Print this page

Weil-McLain 2 Series Manual page 25

Commercial condensing gas-fired water boilers
Hide thumbs Also See for 2 Series:

Advertisement

®
SlimFit
Series 2
Venting/combustion air — options
Vent and air piping materials — Use only the materials listed below, ensuring that all materials meet local
codes (see Figure 96, page 105 for vent/air part/kit numbers)
Duravent / M&G – Polypro
Centrotherm Eco Systems – InnoFlue
Single-wall
Heat Fab, Inc. — Saf-T-Vent
Z-Flex, Inc. — Z-Vent II
stainless
Dura-Vent — FasNSeal ™
steel
Metal-Fab, Inc. — CORR/GUARD
See Note 1 for additional requirements for using PVC
on the exhaust.
See Note 2.
See Note 1 for additional requirements for using PVC
on the exhaust.
See Note 2.
See Note 2.
Notes:
1.
PVC can only be used on the exhaust of a boiler after 10 linear feet of CPVC pipe. All fittings within the first 10 feet
must be CPVC. See Figure 23, page 26 .
2.
For CPVC/PVC , See Figure 96, page 105 for SlimFit adapters to connect boiler connection to CPVC/PVC pipe.
Every joint on vent and air piping must include a locking collar. Failure to supply locking collars could result in vent/air piping
leakage. All PVC and CPVC joints should be permanently joined using the suitable primer and cement for the vent material.
DO NOT USE: Cellular core PVC (ASTM F891), cellular core CPVC, or Radel® (polyphenolsulfone) pipe or any other material
not listed in the table above.
DO NOT mix piping from different pipe manufacturers unless using adapters specifically designed for the purpose by the
manufacturer.
Part number 550-100-180/0917
COMMERCIAL CONDENSING GAS
®
-
FIRED WATER BOILER
Certified for Category IV
and direct vent appliance
venting
Certified for Category IV
®
and direct vent appliance
venting
Certified for Category IV
and direct vent appliance
venting
Certified for Category IV
and direct vent appliance
venting
Certified for Category IV
and direct vent appliance
venting
Certified for Category IV
and direct vent appliance
venting
ANSI/ASTM D1785
ANSI/ASTM D2665
ANSI/ASTM F441
ANSI/ASTM D2564
(cement)
ANSI/ASTM F656
(primer)
ANSI/ASTM F493
(cement)
Primer that is approved
for CPVC.
Use only a Primer and
Cement that is suitable
for joining CPVC and
PVC pipe.
— Boiler Manual
Canada
Plastic vent pipe must be certified to
ULC S636 if required by local codes
Plastic vent pipe must be certified to
ULC S636 if required by local codes
Certified for Category IV and direct vent
appliance venting
Certified for Category IV and direct vent
appliance venting
Certified for Category IV and direct vent
appliance venting
Certified for Category IV and direct vent
appliance venting
Plastic vent pipe must be certified to
ULC S636 if required by local jurisdiction.
Air pipe can be any of those listed at left if
acceptable by local codes.
Plastic vent pipe must be certified to
ULC S636 if required by local jurisdiction.
Air pipe can be any of those listed at left if
acceptable by local codes.
Plastic vent pipe must be certified to
ULC S636 if required by local jurisdiction.
Air pipe can be any of those listed at left if
acceptable by local codes.
ULC S636 rated Primers and Cements
ULC S636 rated Primers and Cements
ULC S636 rated Primers and Cements
25