Battery Alarm Wiring - Sargent 2600 Series Instructions For Installation Manual

Low-energy swing door operator
Table of Contents

Advertisement

Power Alarm - Terminations 1 & 2 on the
Fire Adapter Board
Normally Open Contacts close when the
main 115 VAC power is disrupted. This
action is unaffected by the jumper
positions or loss of battery power.
WARNING:
be properly set with connectors from an
approved fire system. Check your local
code requirements.
Fire Alarm Detection Jumper
JUMPER POSITION
"ON"
"OFF"
Battery Alarm Jumper
JUMPER POSITION
"ON"
"OFF"
Fire Alarm jumpers MUST
FUNCTION / OPERATION
Normally Open Fire Alarm contact
required
Normally Closed Fire Alarm contact
required
FUNCTION / OPERATION
Maintained Low Battery Alarm:
Normally Open contacts 3 & 4 close,
initiating alarm. Must be Reset by
push button.
Momentary Low Battery Alarm: Low
or disconnected battery condition
close contacts 3 & 4 momentarily.
SET ALARM JUMPERS
BATTERY ALARM AND FIRE ADAPTER
1
POWER ALARM TERMINATIONS
2
3
BATTERY ALARM TERMINATIONS
4
5
REMOTE FIRE
6
7
ALARM N.C. CONTACT
8
9
INTERNAL CONNECTIONS
13