R
e
Reason
The return temperature has exceeded the blocking temperature but not the lock-out
temperature.
Cause:
An external heat source (CHP, heat pump etc.) has heated the return temperature above the blocking temperature.
Corrective Action:
Reduce pre heat temperature of the external heat source.
Cause:
The external heating controls suddenly close causing excessive return water temperature.
Corrective Action:
Dampen the reaction time of the external heating control system to prevent sudden boiler temperature rise.
Display message
F
l
Reason
The flue gas temperature has exceeded the blocking temperature.
Cause:
Heat exchanger polluted and not able to effectively transfer heat to the system water.
Corrective Action:
Check and clean the heat exchanger.
Cause:
Defective (partially shorted) flue gas sensor or sensor connection.
Corrective Action:
Check for moisture in the sensor connections or replace sensor.
Cause:
There is no water in the unit while firing.
Corrective Action:
Bleed all air from the unit so the heat from combustion can be transferred to the water and won't leave through the flue
Cause:
Heat exchanger failure.
Corrective Action:
Contact Lochinvar Limited for further guidance.
Display message
A n
Reason
The controller received a new heat demand too soon after the last heat demand finished.
Cause:
System water temperature cooling and causing a heat demand within the anti-cycling time period.
Corrective Action:
Dampen external heating system controls to slow down the cooling time of the heating medium (water).
Increase system volume to act as a buffer between the boiler circuit and heating circuit.
Cause:
Rapid opening and closing of external thermostat
Corrective Action:
Check switching differential of on/off thermostat
t
u
r
n
t
e m p
u
e
t
e m p
h
t
i
c
y
c
l
e
t
h
i
g
h
9
9
9
,
5
h
r
s
i
g
h
9
9
9
,
5
h
r
s
i
m e
9
9
9
,
5
h
r
s
89

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cp-m+120Cp-m+150Cp-m+60Cp-m+80Cp-m+180Cp-m+100

Table of Contents