12.5

SERVICE FUNCTION

The following figure describes how to use the service function.
Operating screen:
H E A T
> > >
Press [SERVICE] and hold for 3 seconds.
The burner will start and show the display below.
Operating screen:
H E A T
> > >
"HEATING": The appliance is operating as a heating boiler.
"Service": It is operating in the service mode.
"26% ": The burner is firing at 26% .
"90,0
"60,0
Model
Max. set point* - (RPM)
Max. actual** - (RPM)
Margin on actual - (RPM)
TABLE 12.1
* The maximum rpm that the controller is to use as a set point.
** The maximum rpm that the fan is actual able to run.
The maximum actual rpm can be lower than the maximum rpm set point. This is because the fan is not able to
reach the maximum rpm set point, due to the unit's resistance. The tolerance varies according to the design of
each specific unit. The relation between the maximum rpm set point and the maximum actual rpm is given in this
table. This table applies also to the service and "Schornsteinfeger" function of the boiler.
I N G : S T A N D
o
:
1 2 3 .
4
C (
I N G : S e r v
o
9 0 .
0
C
(
o
C": Max. allowable water temp. during service.
o
C": Actual measured water temp. (when P5BJ active).
Press [SERVICE] to exit. The unit will go to the operating screen.
Press [ON/OFF] for 3 seconds to exit. The unit will be switched off.
By using the [▲] & [▼] buttons the burner firing rate % can be changed.
Press [MENU] to access the main menu.
Press [MENU] to return to the service menu.
Use [◄] & [►] buttons to browse through the monitor screens.
Press [MENU] to go to the operation menu or the service mode.
Press [SERVICE] to exit the service mode.
The unit will return to the standard operation display.
FIGURE 12.6
CP-M+60
CP-M+80
6500
6500
6500
6500
+/- 50
+/- 50
MAXIMUM COMBUSTION FAN SPEED
- B Y
o
1 2 3 .
4
C )
i
c e
2 6 %
o
6 0 .
0
C )
SERVICE MODE
CP-M+100
CP-M+120
CP-M+150
6500
6500
6230
6095
+/- 175
+/- 175
+/- 50
Or
CP-M+180
5700
5700
5700
5700
+/- 50
50