2. Installation procedure 【Applicable model : Group B】
●To protect the wires connected to M-NET board from the edges of 
 sheet-metal component, paste the insulation on the edge surface of panel
 sheet-metal before proceeding with the following work.
1
Paste insulation sheet ③ on sheet-metal so that it 
completely envelops the edge surface of sheet-metal.
(When viewed from the side of Electric box)
①M-NET board
2
Control board
(When viewed from the side of Electric parts box)
L
N
S1 S2 S3
M-NET Converter PAC-SF81MA-E
7
3
CENTRALIZED CONTROL(M-NET)
4
B G 7 9 H 7 4 4 H 0 2
1
     Pate insulation sheet  ③ on sheet-metal 
so that it completely envelops the edge 
surface of sheet-metal.
     Install M-NET board ① (with insulation 
2
sheets and supports) on the side of 
Electric box so that the rotary switch 
faces up (at the four points indicated by 
arrows).
     ※Push it firmly until you hear it 
click .  
     Use terminal screw ⑦ to secure terminal 
3
block⑥ 
     ※Terminal block⑥ has a round boss for 
positioning:Fit the round boss into the 
positioning hole in steel-plate.
     Paste label ⑧ under terminal block ⑥
4
     Use lead wire-A ⑨ to connect CN5 of 
5
M-NET board ① connection and 
CNMNT of outdoor control board.
     ※Caution
Wire Marking:INV type, Connector 
color:Red Always make sure that the 
markings and the applicable model 
match. If used incorrectly, parts could 
be damaged.
Use lead wire-C ⑪ to connect CND of 
6
M-NET board ① connection and 
CNVMNT of outdoor control board. 
Use lead wire-D ⑫ to connect CN2M of 
7
M-NET board ① connection and 
terminals A and B of terminal block ⑥ 
Polarity is not a concern.
※Connect the wire firmly making sure 
that the screws on terminal block are 
not loose.
     
   The lead wires should be tied together 
8
with the other lead wires with    
     the pull tight ⑭ not to loose.
Wiring length is adjusted according to 
apparatus.
   It progresses to the  page
  3.Wiring method for M-NET
Note1:Use ground wire and screw ⑬ as 
required to connect the shield of 
M-NET transmission line to the unit.
Note2:Take great care that no lead wire is 
caught on anything when instaling 
panels.