Mitsubishi Electric PAC-SF81MA-E Installation Manual page 4

M-net converter

Advertisement

2. Installation procedure 【Applicable model : Group A】
●To protect the wires connected to M-NET board from the edges of 
 sheet-metal component, paste the insulation on the edge surface of panel
 sheet-metal before proceeding with the following work.
③Insulation sheet
(Top view of Electric box)
Control board
Chamfered section
Noise filter
Power board
(When viewed from the side of Electric box)
Noise filter
E-212
M-NET Converter PAC-SF81MA-E
③Insulation sheet
1
CN2M
CN5
SW12
SW11
CND
4
Terminal block (M-NET)
5
6
L
N
S1 S2 S3
1
     Affix insulation sheets and ③ to the 
backside of the flange surface on the 
top of the side panel.
2
     Starting from the bottom, mount 
lnsulation Sheet ③ to the  L  bend 
section on the back of the noise filter 
mounting panel.
3
     Position the chamfered section of Plate  
② so that it faces the fan side (the left 
side of the drawing) and mount it using 
Screw ⑤.
4
     As shown in the illustration, position 
M-NET board ① (insulation sheet, with 
support) on the four corners of Plate ② 
so that the DIP switches (SW11, SW12) 
①M-NET board
are on the terminal block side and then 
mount.
     ※Push it firmly until you hear it  click
2
3
5
     Use terminal screw ⑦ to secure terminal 
block ⑥ 
③Insulation sheet
     ※Terminal block ⑥ has a round boss 
⑤Screw
for positioning:Fit the round boss into 
②Plate
the positioning hole in steel-plate.
6
     Paste label ⑧
Terminal block
7
     Use lead wire-A⑨ to connect CN5 of 
M-NET board ① connection and 
CNMNT of outdoor control board.
     ※Caution
Wire Marking:INV type, Connector 
color:Red Always make sure that the 
markings and the applicable model 
match. If used incorrectly, parts could 
be damaged.
8
Use lead wire-C ⑪ to connect CND of 
M-NET board ① connection and 
CNVMNT of outdoor control board. 
9
Use lead wire-D ⑫ to connect CN2M of 
M-NET board ① connection and 
terminals A and B of terminal block ⑥ 
Polarity is not a concern.
※Connect the wire firmly making sure 
that the screws on terminal block are 
not loose.
     
   The lead wires should be tied together 
10
with the other lead wires with    
     the pull tight ⑭ not to loose.
Wiring length is adjusted according to 
apparatus.
Terminal block
   It progresses to the xx page
  3.Wiring method for M-NET
Note1:Use ground wire and screw ⑬ as 
Note2:Take great care that no lead wire is 
required to connect the shield of 
M-NET transmission line to the unit.
caught on anything when instaling 
panels.