6.
Indication of operation standby:
This icon indicates that the unit is precooling/preheating. The
unit's start-up is delayed until precooling/preheating is finished.
Precooling/preheating means that the heat reclaim ventilation
units are NOT started while linked air conditioners are starting
up, for example, before office hours.
During this period, the cooling or heating load is reduced to
bring the room temperature to the set temperature in a short
time.
7.
Indication of centralized control:
When a remote controller for air conditioners or devices for
centralized control are connected to the heat reclaim ventilation
units, this indication may be displayed.
While this indication is displayed, you may NOT be able to turn
the heat reclaim ventilation units on or off, or use the timer
function with the controller of the heat reclaim ventilation unit.
8.
Indication of air filter cleaning
When the display shows "
9.
Filter signal reset button
10. Inspection button
Use this button only when servicing the unit.
11. Schedule timer button:
This button enables or disables the schedule timer.
12. Time adjust button:
.
13. Programming button:
To set the timer
1
Press the schedule timer button.
2
Press the time adjust button to set the time.
3
Press the programming button to save the setting.
Independent system
When connecting to remote controller for HRV
HRV
P1 P2
P1 P2
1
3
1
Master unit
2
Slave unit
3
Switch position: Slave
Factory settings: Do NOT change the switch
settings. SS1 is a setting switch for special
NOR
purposes. Changing the settings will stop the unit
from operating normally.
H
M
For raising the remote-controlled ventilation air flow rate from "High"
to "Ultra-High", connect the remote controller for the air-conditioner to
HRV and make settings on site.
(Refer to
"List of settings" on page
Keep the switch on the PCB at the factory setting.
Installation manual
15
", clean the filter.
/
or
.
/
.
HRV
P1 P2
6
P1 P2
5
2
4
4
Switch position: Master
5
Remote controller for HRV
6
Maximum connection line length:
500 m
12.)
Wiring and connections in combination with
"VRV-SYSTEM"
Standard 1-group linked-control system
I
The remote control of the air conditioner can be used to control
up to 16 air conditioner indoor units and HRV units.
I
Initial settings can be made for the functions of the HRV units
(pre-cool/pre-heat, ventilation air flow, ventilation mode and
"Fresh-Up").
Use the remote controller of the air conditioner to make the initial
settings for the HRV units.
Refer to "Initial setting" under Item
VRV
P1
P2
1
Remote controller for air
conditioner
2
Remote controller for HRV
Pre-cool/pre-heat function
When the pre-cool/pre-heat function is set, the HRV unit switches on
at the preset time (30, 45 or 60 minutes) after the VRV-system air
conditioner begins cooling or heating operation. The function is set
OFF at the factory. Therefore, to use this function, the initial setting
must be made using the remote controller of the air conditioner.
If the air conditioner is re-started within two hours after the operation
was stopped, this function does not operate.
Example 1:
To switch on the pre-cool/pre-heat function, and turn on the HRV unit
60 minutes after the air conditioner is turned on.
Set the mode No. to "17" for group control, or "27" for individual
control, the setting switch No. to "2" and the setting position No.
to "02"
Set the mode No. to "17" for group control, or "27" for individual
control, the setting switch No. to "3" and the setting position No.
to "03"
Example 2:
To switch the ventilation air flow to ultra high setting. (The units are
set at the high air flow setting at the factory)
Set the mode No. to "17" for group control, or "27" for individual
control, the setting switch No. to "4" and the setting position No.
to "02"
Example 3:
Air ventilation rate
setting using remote
Default factory settings
control
Low
Low (L) air flow rate
High
High (H) air flow rate
When the remote controller is connected, keep the switches on the
heat reclaim ventilation unit PCB at the default factory settings.
Factory settings: Do NOT change the switch
settings.
NOR
SS1 is a setting switch for special purposes.
H
Changing the settings will stop the unit from
operating normally.
M
"Configuration" on page
HRV
3
P1 P2
P1P2
P1 P2
1
2
3
Connecting line can be extended
up to 500 m maximum
When set as in example
2
Low (L) air flow rate
Ultra-high (UH) air flow
rate
VAM150+250FC
Total Heat Exchanger
HRV (Heat Reclaim Ventilation)
4P586307-1 – 2019.06
10"