Mains Power Supply Line - SignaMax MicroDC Technical Manual

Data centers for the edge
Table of Contents

Advertisement

The MicroDC comes with 2,5m / 99 inches length special PVC
hoses (12mm / 0,5 inch inner Ø and 17mm / 0,66 inch outer Ø
dimensions). This pipe should be connected to the tube and
should be driven to the first available drain (gutter or spout).
If the first drain is more than 2 meters / 80 i̇ nches away from
the MicroDC, then the installer might need to extend these
PVC hoses.
Please take great care to choose the most proper position
to place your MicroDC. You should choose a well-ventilated
place. For example a good choice is inside a room with an
open window or inside an air condition room. The MicroDC
should not be exposed to any possible drops of water coming
from the open window. When the cooling device is operating,
the generated noise (mainly coming from the embedded
compressor) might be annoying. Please avoid placing the
MicroDC close to any infants. Please visit the room where
the MicroDC stands quite often (especially after the first
installation) to secure that the environmental conditions meet
the operating limits.

2.3 Mains Power Supply Line

A clean, unloaded and direct single phase power supply
line shall be present to supply all the power needed for the
equipment to be connected to the MicroDC. This line shall be
protected from spikes or surges through protection devices.
A residual current device must be present in order to detect
ground faults - leakage of current to somewhere other than
the neutral and line wires (like the ground wire or a person).
This device shall protect any engineer while installing or
while maintenance procedures. The line shall be protected
www.signamax.com
Micro Data Center Technical Manual 7

Advertisement

Table of Contents
loading

Table of Contents