SignaMax MicroDC Technical Manual

Data centers for the edge

Advertisement

Quick Links

Data Centers for the EDGE
Technical Manual of Micro Data Center
www.signamax.com

Advertisement

Table of Contents
loading

Summary of Contents for SignaMax MicroDC

  • Page 1 Data Centers for the EDGE Technical Manual of Micro Data Center www.signamax.com...
  • Page 2: Table Of Contents

    Technical Manual of MicroDC Table of Contents Important Safety Instructions Scope Pre-installation precautions Cabinet Cooling unit Mains Power Supply Line Installation Required Setup Equipment Cabinet Installation Cooling Unit Secondary Equipment Maintenance Cooling device Troubleshooting Wheels Cooling Service Log Certificates www.signamax.com...
  • Page 3: Important Safety Instructions

    Ensure the MicroDC has proper ventilation. Never block or insert objects into the ventilation holes or other openings. Maintain a minimum clearance of 500mm /19.7 inches in front, rear and top of the MicroDC for proper air flow and cooling. www.signamax.com Micro Data Center Technical Manual 3...
  • Page 4: Scope

    The scope of this technical manual includes four phases; first it relies on helping the end user arrange / prepare the site where the MicroDC is going to be installed. Second it explains how the MicroDC should be properly handled, installed, connected and operated.
  • Page 5: Pre-Installation Precautions

    E:\pdmview\canovate\Standart Urunler\05-Micro Datacenter Kab 2 Pre-installation 2.1 Cabinet MicroDC cabinet is coming in multiple versions in terms of fixing. This information is usually pre-defined at the ordering procedure. It usually comes as floor standing with or without wheels. This means that you don’t have to worry about fixing the cabinet on the floor.
  • Page 6: Cooling Unit

    MicroDC has no wheels, the standing place is very important and should be initially decided, as later on it will be very difficult but also dangerous and not recommended to move. 2.2 Cooling unit Attached to the MicroDC there is a Top Mountable Air- Condition unit.
  • Page 7: Mains Power Supply Line

    The MicroDC comes with 2,5m / 99 inches length special PVC hoses (12mm / 0,5 inch inner Ø and 17mm / 0,66 inch outer Ø dimensions). This pipe should be connected to the tube and should be driven to the first available drain (gutter or spout).
  • Page 8: Installation

    All the installation must be held by professional engineers and previously been trained to properly handle the MicroDC. Note: The MicroDC is not intended to be used in an occupied office environment, due to potentially high noise levels during the cooling operation. Install the MicroDC in a computer room or in any other room where people are normally present only for maintenance.
  • Page 9 MicroDC. The MicroDC is standing on a wooden pallet. All the way round there are lots of thick cartons used for protection of the cabinet against possible damage to the surface color.
  • Page 10 Step 2: Remove the nylon slowly and gently using the utility knife or any other suitable cutting tool; take care not to scratch the color of the MicroDC cabinet. Step 3: Remove all carton pcs surrounding the MicroDC. Those cartons are loose so there is no need to use any tool at the moment.
  • Page 11 Note: Known the weight and size of the MicroDC, it is possible that the MicroDC may tip over while moving. The MicroDC must be removed from the shipping crate using a minimum of 2 people.
  • Page 12 Each pair consists of two vertical rails. Each vertical rail is fixed on the rack cabinet of MicroDC by the use of 2 or 3 screwing points, depending on the height of the MicroDC.
  • Page 13 Use the Allen key size 4 to unscrew the (M6x12) screws positioned either on the top or to the bottom of the MicroDC. In case your MicroDC is a 42U edition, it includes a center fixing point (side support rail inside the MicroDC cabinet) then by the use of the Torx key size T25 you can unscrew the (M5x12) positioned on the side support rail.
  • Page 14: Cooling Unit

    6 Ampere. As per the manufacturer a fuse of 10A-16A rated shall be used. Please pay attention this circuit breaker must be rated tripping B with equal or more www.signamax.com Micro Data Center Technical Manual 14...
  • Page 15 Inside the MicroDC there is one plastic hose. It fits to the Air-Condition Cooling Unit, outside of the MicroDC. It is used for any condensation water may be produced.
  • Page 16: Secondary Equipment

    Thus the installer should choose the proper placement for this MicroDC i.e. close to an open window or in a well- ventilated position. Please refer to the respective user manual of the cooling unit for any more detailed information on how to operate and setup the cooling unit.
  • Page 17: Maintenance

    PDU. 4 Maintenance One of the biggest advantages of the MicroDC is the very low maintenance cost needed in order the system to operate and function as brand new.
  • Page 18: Troubleshooting

    You may use a lubricant spray as well The brakes (where available) are Release the brakes and then preventing from sliding try to move the MicroDC once again www.signamax.com Micro Data Center Technical Manual 18...
  • Page 19: Cooling

    Capacitor for compressor starting failed (where pres- Call a refrigeration expert ent) Call a refrigeration expert Compressor motor electrical Change the contractor failure High pressure safety switch failed Compressor contactor failed (where present) www.signamax.com Micro Data Center Technical Manual 19...
  • Page 20 This is not a malfunction of the cooling unit. closed below IP54 Seal enclosure openings, i.e. for passage and upward path of wires The enclosure/cooling unit Check seal and remedy connecting seal has been fitted incorrectly www.signamax.com Micro Data Center Technical Manual 20...
  • Page 21: Service Log