Connecting up

6.4 Signaling contact

6.4
Signaling contact
Information on the signaling contact
● The signaling contact is a floating switch that signals error statuses by opening the
contact.
The signaling contact must be operated within the range of the operating voltage.
If an error/fault occurs, the signaling contact opens. In normal operation, the signaling
contact is closed.
● The signaling contact is connected using a 2-pin plug-in terminal block (spring-loaded
terminal). The terminal block ships with the device and can also be ordered as a spare
part.
● To wire up the signaling contact, use a copper cable of category 18-12 AWG or a cable
with a cross-section of 0.75 to 2.5 mm
NOTICE
Damage due to voltage being too high
The signaling contact can be subjected to a maximum load of 100 mA (safety extra-low
voltage SELV, 24 VDC).
Higher voltages or currents can damage the device!
Position and assignment
Figure 6-2
Pin number
Pin 1
Pin 2
60
Position of the signaling contact on the SCALANCE XM-400 and the assignment of the
terminal block
.
2
Assignment
F1
F2
Operating Instructions, 09/2018, C79000-G8976-C306-08
SCALANCE XM-400