Programming; Calibration: 0 - 100% / 4 - 20 Ma; Relays - Siemens SITRANS CU02 Operating Instructions Manual

Acoustic sensors
Table of Contents

Advertisement

Programming

Note
Security must be disabled to set programming functions.
7.1

Calibration: 0 - 100% / 4 - 20 mA

● calibrate the 0% / 4 or 20 mA level by entering the value of V
● calibrate the 100% / 20 or 4 mA level by entering the value of V
between P 2 and P 3 must be at least 0.2 V for full 4 - 20 mA span.
7.2

Relays

For precise determination of alarm setpoints, view the run display in percent and run the
material or machinery through its range of operation. Note the % values corresponding to the
alarm points.
Note
The setpoints should be 0.50 V above or below the fault/no fault condition if the sensor is
installed in high RF noise locations.
SITRANS CU02
Operating Instructions, 03/2017, A5E40873245_AA
7
into P 2
norm
into P 3. The difference
abn
23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents