Programming
Note
Security must be disabled to set programming functions.
7.1
Calibration: 0 - 100% / 4 - 20 mA
● calibrate the 0% / 4 or 20 mA level by entering the value of V
● calibrate the 100% / 20 or 4 mA level by entering the value of V
between P 2 and P 3 must be at least 0.2 V for full 4 - 20 mA span.
7.2
Relays
For precise determination of alarm setpoints, view the run display in percent and run the
material or machinery through its range of operation. Note the % values corresponding to the
alarm points.
Note
The setpoints should be 0.50 V above or below the fault/no fault condition if the sensor is
installed in high RF noise locations.