Section 5
GOOSE
5.4.4
5.4.4.1
40
The third-party devices have separate tools for creating the ICD/CID/
SCD file.
SCD files can be imported to a project only once. If a new device needs
to be later added to the configuration, it must be first created using the
Create New IED function after which the Update IED function can
be used to import the related CID or ICD file. Another alternative is to
create a new project in IET600 and import the whole SCD file from
PCM600. The existing IEC 61850 configuration including GOOSE
remains if the changes made in IET600 have been already imported to
PCM600.

Configuring a GOOSE publisher with IET600

To control the GOOSE data publishing, such as addressing, every publisher device
must have at least one data set for GOOSE data and one GOOSE control block.
1.
Group the data to a data set sent to IEC 61850 station bus.
2.
Define the GOOSE control block.
The protection relay can send single binary, double binary, integer and
floating point data values with a quality attribute. A quality attribute
is used at the receiver side to check data validity.

Creating a GOOSE data set with IET600

The sending data set used by the GOOSE control block must be defined. With the
protection relays of this product series, the sending device can have a maximum of 80
data attributes in GOOSE data sets. To minimize the message-handling load in
receiving and sending protection relays, the recommendation is to divide data
attributes to a maximum of 20 per data set.
All data sets must be configured under the logical node LLN0 and must be provided
with names unique within the device. The protection relays allow a maximum of four
GOOSE control blocks, which effectively limits the protection relay to four data sets
for GOOSE as there is a one-to-one correspondence between the GOOSE control
blocks and GOOSE data sets. Typically it is sufficient to define a single data set and
control block for an application. However, it is recommended to use a separate data set
and corresponding control block for analog values.
1.
Select the IEDs tab in the navigation pane.
2.
Click the IED node.
3.
Click the Datasets tab in the editor pane.
1MRS757809 C
REC615 and RER615
Engineering Guide